Plan Review Notes For Permit 14050312 |
Permit Number |
14050312 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-05-09 07:48:50 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE | | BUILT UP ROOFING MATERIALS THAT WILL BE USED ON THE | | FLAT ROOF AS REQUIRED BY DCA RULE 9N-3. | | | | 2) IF THE MAXIMUM DESIGN PRESSURE FOR THE FLAT ROOF | | SYSTEM IS LESS THAN THE REQUIRED UPLIFT PRESSURES, | | SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | CALCULATIONS FOR ENHANCED FASTENING IN THE CORNER AND | | PERIMETER ROOF AREAS IF IT IS ALLOWED BY THE PRODUCT | | APPROVAL. FBCR 301.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|