2014-05-17 12:01:30 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. AN ATTEMPT WAS MADE TO COMPLETE OR CORRECT THE |
| SHUTTER INSTALLATION SCHEDULES, BUT SUBSTRATE CANNOT BE |
| DETERMINED. THE CLEAR PANEL INSTALLATION STATES THAT |
| THE SUBSTRATE IS CONCRETE, BUT THE OTHER TWO SCHEDULES |
| STATE THAT THE SUBSTRATE IS BLOCK. AS THE ACTUAL |
| SUBSTRATE CANNOT BE DETERMINED AT THIS TIME, A COMPLETE |
| REVIEW CANNOT BE PERFORMED. |
| |
| MOST STRUCTURES OF CBS CONSTRUCTION HAVE A SUBSTRATE OF |
| CONCRETE AT THE TOP, FILLED BLOCK AT THE BOTTOM (CBS). |
| SOME HOUSES WERE BUILT WITH THE ROYAL WALL SYSTEM, |
| WHICH WOULD BE CONCRETE TOP AND BOTTOM. IF JOB |
| CONDITIONS REQUIRE THAT THE TOP MOUNTING IS ABOVE THE |
| LINTEL, THE SUBSTRATE AT THE TOP WOULD ALSO BE BLOCK. |
| GROUT FILLED BLOCK WOULD BE "MASONRY" SUBSTRATE UNLESS |
| THE PRODUCT APPROVAL INCLUDES GROUT FILLED BLOCK. |
| |
| 2. CLEAR PANEL INSTALLATION SCHEDULE WAS NOT COMPLTED. |
| I ATTEMPTED TO COMPLETE THIS INFORMATION FOR YOU BASED |
| ON HIGHLIGHTED INFORMATION ON THE PRODUCT APPROVAL, BUT |
| IT IS NOT CLEAR WHY ALL OF THE OPENINGS FOR THE CLEAR |
| PANELS ARE CONCRETE, BUT NOT FOR OTHER OPENINGS. |
| |
| COMPLETE THE INSTALLATION SCHEDULE FOR THE CLEAR |
| PANELS. |
| |
| 2. THE FLORIDA PRODUCT APPROVAL REFERRED TO ON ALL OF |
| THE INSTALLATION SCHEDULES IS 5133, BUT THIS PRODUCT |
| APPROVAL WAS NOT SUBMITTED. PLEASE REVISE TO REFER TO |
| THE CORRECT PRODUCT APPROVAL. |
| |
| 3. FOR THE ACCORDION SHUTTERS, THE SHUTTER CONNECTION |
| MOUNTING TYPE SHOULD CORRELATE WITH THE ANCHOR CHARTS. |
| FOR INSTANCE, INSTALLATION SCHEDULE FOR OPENING 1 |
| STATES "CEILING/WALL". SEE SHEETS 12 THROUGH 14, |
| MOUNTING TYPES ARE NAMED "A" THROUGH "L". MANY THINGS |
| ARE HIGHLIGHTED IN THE CHARTS, BUT NOTHING HIGHLIGHTED |
| FOR G, THE ONLY MOUNTING TYPE WITH A "CEILING" |
| DESCRIPTION. SOME OF THE ITEMS HIGHLIGHTED REQUIRE A |
| CONCRETE SUBSTRATE, BUT BLOCK IS STATED AS SUBSTRATE. |
| |
| 4. FOR THE PANEL, OPENING 25, MOUNTING TYPE PROPOSED IS |
| "75". SEE ANCHOR CHARTS, NAMING CONVENTION USES NUMBERS |
| FROM 1 THROUGH 13, ALONG WITH ALTERNATIVES. |
| |
| IF YOU WISH TO HAVE A MEETING TO GO OVER ALL OF THESE |
| ITEMS AND GUIDANCE AS TO HOW TO COMPLETE THIS FORM, |
| FEEL FREE TO CONTACT ME TO SCHEDULE. QUALIFER MUST BE |
| PRESENT AT THIS MEETING, AND ANY OTHER STAFF MEMBERS |
| ARE WELCOME. |