Plan Review Notes
Plan Review Notes For Permit 14050273
Permit Number 14050273
Review Stop E
Sequence Number 2
Notes
Date Text
2014-05-27 16:04:222ND ELECTRICAL REVIEW DENIED. THE ELECTRICAL SYSTEM IS
 STILL FOUND TO BE DEFICIENT IN THE FOLLOWING AREAS
 BASED ON 2008 EDITION OF THE NEC AND THE 2010 FBC. SEE
 COMMENTS BELOW:
  
 1) GROUNDING ELECTRODE CONDUCTOR IS IMPROPERLY SIZED
 250.66, THE GROUNDING ELECTRODE CONDUCTOR FOR A 300AMP
 SERVICE IS REQUIRED TO BE A #2CU MINIMUM.
  
 2) AN INTERSYSTEM BOND STRIP IS REQUIRED PER 250.94
  
 3) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. NEC 210.8. ALL OUTLETS IN THE GARAGE
 SHALL BE GFCI PROTECTED. INCLUDING THE GARAGE DOOR
 OPENERS.
  
 4) RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT
 ALONG THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. NEC 210.52 (A)(2).
 THERE ARE SEVERAL AREAS THROUGHOUT THE HOME TO BE
 ADDRESSED. THIS INCLUDES FIXED PANELS. "THE SPACE
 OCCUPIED BY FIXED PANELS IN EXTERIOR WALLS, EXCLUDING
 SLIDING PANELS"
  
 7) IF THE RESIDENCE HAS GAS APPLIANCES, AN ATTACHED
 GARAGE OR A FIRE PLACE A CARBON MONOXIDE DETECTOR IS
 REQUIRED WITHIN TEN FEET OF EACH ROOM USED FOR
 SLEEPING. FBC R314, 315
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE POOL, AND
 DOCK.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]