2014-05-27 16:04:22 | 2ND ELECTRICAL REVIEW DENIED. THE ELECTRICAL SYSTEM IS |
| STILL FOUND TO BE DEFICIENT IN THE FOLLOWING AREAS |
| BASED ON 2008 EDITION OF THE NEC AND THE 2010 FBC. SEE |
| COMMENTS BELOW: |
| |
| 1) GROUNDING ELECTRODE CONDUCTOR IS IMPROPERLY SIZED |
| 250.66, THE GROUNDING ELECTRODE CONDUCTOR FOR A 300AMP |
| SERVICE IS REQUIRED TO BE A #2CU MINIMUM. |
| |
| 2) AN INTERSYSTEM BOND STRIP IS REQUIRED PER 250.94 |
| |
| 3) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES |
| INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION |
| FOR PERSONNEL. NEC 210.8. ALL OUTLETS IN THE GARAGE |
| SHALL BE GFCI PROTECTED. INCLUDING THE GARAGE DOOR |
| OPENERS. |
| |
| 4) RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT |
| ALONG THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A |
| RECEPTACLE OUTLET. NEC 210.52 (A)(2). |
| THERE ARE SEVERAL AREAS THROUGHOUT THE HOME TO BE |
| ADDRESSED. THIS INCLUDES FIXED PANELS. "THE SPACE |
| OCCUPIED BY FIXED PANELS IN EXTERIOR WALLS, EXCLUDING |
| SLIDING PANELS" |
| |
| 7) IF THE RESIDENCE HAS GAS APPLIANCES, AN ATTACHED |
| GARAGE OR A FIRE PLACE A CARBON MONOXIDE DETECTOR IS |
| REQUIRED WITHIN TEN FEET OF EACH ROOM USED FOR |
| SLEEPING. FBC R314, 315 |
| |
| NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE POOL, AND |
| DOCK. |
| |