2014-05-18 09:04:28 | 1ST REVIEW: |
| |
| 1) FBC-R-M 1602.4 PROVIDE BALANCED AIR RETURN AT THE |
| MASTER BEDROOM I DO NOT SEE A RAG OR JUMPER FOR THIS |
| ROOM ON THE PLAN. |
| |
| 2) FBC-EC 403.2.5 PROVIDE A SIZING CALCULATION: PRVIDE |
| A SIZING CALCULATION THAT IS CONSISTENT WITH THE |
| INFORMATION ON THE PLAN. THE MANUAL J MODEL NUMBER FOR |
| SYSTEM 2 DOES NOT MATCH THAT SPECIFIED UPON THE PLAN. |
| PROVIDE THE SENSIBLE AND LATENT COOLING CAPACITY ON THE |
| EQUIPMENT SCHEDULE FOR EACH SYSTEM ON THE PLAN. |
| |
| 3) FBC-R M1305.1.3 APPLIANCES IN ATTICS. INDICATE ON |
| THE PLAN THE FOLLOWING, PARTICULARLY THE INTENT TO |
| PROVIDE SOLID DECKING: ATTICS CONTAINING APPLIANCES |
| SHALL BE PROVIDED WITH AN OPENING AND A CLEAR AND |
| UNOBSTRUCTED PASSAGEWAY LARGE ENOUGH TO ALLOW REMOVAL |
| OF THE LARGEST APPLIANCE, BUT NOT LESS THAN 30 INCHES |
| (762 MM) HIGH AND 22 INCHES (559 MM) WIDE AND NOT MORE |
| THAN 6 FEET (1829 MM) LONG MEASURED ALONG THE |
| CENTERLINE OF THE PASSAGEWAY FROM THE OPENING TO THE |
| APPLIANCE. THE PASSAGEWAY SHALL HAVE CONTINUOUS SOLID |
| FLOORING IN ACCORDANCE WITH CHAPTER 5 NOT LESS THAN 24 |
| INCHES (610 MM) WIDE. A LEVEL SERVICE SPACE AT LEAST 30 |
| INCHES (762 MM) DEEP AND 30 INCHES (762 MM) WIDE SHALL |
| BE PRESENT ALONG ALL SIDES OF THE APPLIANCE WHERE |
| ACCESS IS REQUIRED. THE CLEAR ACCESS OPENING DIMENSIONS |
| SHALL BE A MINIMUM OF 20 INCHES BY 30 INCHES (508 MM BY |
| 762 MM), AND LARGE ENOUGH TO ALLOW REMOVAL OF THE |
| LARGEST APPLIANCE. |
| |
| 4) FBC-R M1305.1.3.1 ELECTRICAL REQUIREMENTS. |
| A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE |
| REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET |
| SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN |
| ACCORDANCE WITH CHAPTER 34. |
| |
| 5) INDICATE UPON THE PLAN COMPLIANCE WITH #2 & #3 |
| BELOW: |
| FBC-R M1305.1.3.2 AIR-HANDLING UNITS AIR-HANDLING UNITS |
| SHALL BE ALLOWED IN ATTICS IF THE FOLLOWING CONDITIONS |
| ARE MET: |
| 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN |
| 6 FEET (1829 MM) OF AN ATTIC ACCESS. |
| 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE |
| UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING |
| PROPERLY. |
| 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO |
| REPLACE THE AIR HANDLER |
| 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL |
| INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS |
| LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL |
| CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST |
| PARAGRAPH IN BOLD: |
| |