2014-05-18 09:04:281ST REVIEW:
  
 1) FBC-R-M 1602.4 PROVIDE BALANCED AIR RETURN AT THE
 MASTER BEDROOM I DO NOT SEE A RAG OR JUMPER FOR THIS
 ROOM ON THE PLAN.
  
 2) FBC-EC 403.2.5 PROVIDE A SIZING CALCULATION: PRVIDE
 A SIZING CALCULATION THAT IS CONSISTENT WITH THE
 INFORMATION ON THE PLAN. THE MANUAL J MODEL NUMBER FOR
 SYSTEM 2 DOES NOT MATCH THAT SPECIFIED UPON THE PLAN.
 PROVIDE THE SENSIBLE AND LATENT COOLING CAPACITY ON THE
 EQUIPMENT SCHEDULE FOR EACH SYSTEM ON THE PLAN.
  
 3) FBC-R M1305.1.3 APPLIANCES IN ATTICS. INDICATE ON
 THE PLAN THE FOLLOWING, PARTICULARLY THE INTENT TO
 PROVIDE SOLID DECKING: ATTICS CONTAINING APPLIANCES
 SHALL BE PROVIDED WITH AN OPENING AND A CLEAR AND
 UNOBSTRUCTED PASSAGEWAY LARGE ENOUGH TO ALLOW REMOVAL
 OF THE LARGEST APPLIANCE, BUT NOT LESS THAN 30 INCHES
 (762 MM) HIGH AND 22 INCHES (559 MM) WIDE AND NOT MORE
 THAN 6 FEET (1829 MM) LONG MEASURED ALONG THE
 CENTERLINE OF THE PASSAGEWAY FROM THE OPENING TO THE
 APPLIANCE. THE PASSAGEWAY SHALL HAVE CONTINUOUS SOLID
 FLOORING IN ACCORDANCE WITH CHAPTER 5 NOT LESS THAN 24
 INCHES (610 MM) WIDE. A LEVEL SERVICE SPACE AT LEAST 30
 INCHES (762 MM) DEEP AND 30 INCHES (762 MM) WIDE SHALL
 BE PRESENT ALONG ALL SIDES OF THE APPLIANCE WHERE
 ACCESS IS REQUIRED. THE CLEAR ACCESS OPENING DIMENSIONS
 SHALL BE A MINIMUM OF 20 INCHES BY 30 INCHES (508 MM BY
 762 MM), AND LARGE ENOUGH TO ALLOW REMOVAL OF THE
 LARGEST APPLIANCE.
  
 4) FBC-R M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
 5) INDICATE UPON THE PLAN COMPLIANCE WITH #2 & #3
 BELOW:
 FBC-R M1305.1.3.2 AIR-HANDLING UNITS AIR-HANDLING UNITS
 SHALL BE ALLOWED IN ATTICS IF THE FOLLOWING CONDITIONS
 ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  