2014-05-19 14:22:37ELECTRICAL REVIEW DENIED. THE ELECTRICAL SYSTEM IS
 FOUND TO BE DEFICIENT IN THE FOLLOWING AREAS BASED ON
 2008 EDITION OF THE NEC AND THE 2010 FBC, FBC RES., FBC
 ENERGY, SEE COMMENTS BELOW.
  
 1) ELECTRICAL SERVICE RISER INDICATES A 300AMP
 DISCONNECT SWITCH WITH A 2/0 FEEDER. THE MINIMUM SIZE
 SERVICE ENTRANCE CONDUCTOR FOR A RESIDENTIAL SERVICE
 ENTRANCE OR FEEDER IS A 250MCM CU. OR 350MCM AL.
  
 2) THE DESIGN OF THE ELECTRICAL SERVICE RISER IS NOT IN
 COMPLIANCE WITH NEC 310.15(B)(6), 240.21. PLEASE SHOW
 OVER CURRENT PROTECTION AND APPROPRIATE FEEDER SIZE FOR
 SUB-PANEL "B"
  
 3) GROUNDING ELECTRODE CONDUCTOR APPEARS TO BE
 IMPROPERLY SIZED FOR BONDING OF ALL SYSTEMS AND PROVIDE
 BONDING OF ALL SYSTEMS AND BUILDING STEEL, AS
 APPLICABLE 250.66, 250.104THE GROUNDING ELECTRODE
 CONDUCTOR FOR A 300AMP SERVICE IS REQUIRED TO BE A #2CU
 MINIMUM.
  
 4) AN INTERSYSTEM BOND STRIP IS REQUIRED PER 250.94
  
 5) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. NEC 210.8. ALL OUTLETS IN THE GARAGE
 SHALL BE GFCI PROTECTED.
  
 6) LUMINAIRES IN CLOTHES CLOSETS. ARTICLE 410.16 (C)(3)
 LOCATION. STATES IN PART , THE MINIMUM CLEARANCE
 BETWEEN LUMINAIRES INSTALLED IN CLOTHES CLOSETS AND THE
 NEAREST POINT OF A STORAGE SPACE SHALL BE AS FOLLOWS:
 "150MM (6") FOR RECESSED INCANDESCENT OR LED LUMINAIRES
 WITH A COMPLETELY ENCLOSED LIGHT SOURCE INSTALLED IN
 THE WALL OR CEILING" OR (4) "150MM (6") FOR RECESSED
 FLUORESCENT LUMINAIRES INSTALLED IN THE WALL OR
 CEILING." PLEASE INDICATE COMPLIANCE WITH THIS SECTION
 OF THE NEC WHERE INSTALLING RECESSED LIGHTING IN
 CLOTHES CLOSETS
  
 7) RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT
 ALONG THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. NEC 210.52 (A)(2).
 THERE ARE SEVERAL AREAS THROUGHOUT THE HOME TO BE
 ADDRESSED.
  
 8) RECESSED LIGHTING TO BE AIR TIGHT AND IC RATED. AT
 LEAST 50% OF THE LAMPS IN PERMANENTLY INSTALLED LIGHT
 FIXTURES SHALL BE HIGH EFFICIENCY. FBC-R 402.4.5, &
 404.1,
  
 9) ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC
 406.11 THOSE OUTLETS IN WET LOCATIONS SHALL BE WEATHER
 RESISTANT NEC 406.8(B)(1)
  
 10) OCCUPIABLE BALCONIES AND PORCHES OVER 20 SQ FT MUST
 HAVE A RECEPTACLE OUTLET GFCI PROTECTED. NEC
 210.52(E)(3).
  
 11) IN KITCHENS, PANTRIES, BREAKFAST ROOMS, DINING
 ROOMS, AND SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE
 OUTLETS FOR COUNTERTOP SPACES SHALL BE INSTALLED IN
 ACCORDANCE WITH NEC 210.52(C)(1) THROUGH (C)(5).
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]