2014-05-18 09:23:08 | 1ST REVIEW: |
| |
| 1) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY |
| DCA RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. SPECIFICALLY, GARAGE DOOR |
| SUBMITTALS. GARAGE DOOR IS MISSING, OTHERS OK. |
| |
| 2) FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE |
| SETBACKS AND BUILDING SEPARATION. THE SITE PLAN AND |
| SURVEY PROVIDED DO NOT MATCH. |
| |
| 3) FBC-110.7 SUPPLY A DRAINAGE DESIGN. NEW CONSTRUCTION |
| ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC |
| SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT |
| PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN |
| COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES. |
| |
| 4) FBC 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE |
| OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION |
| OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS |
| (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE |
| BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION |
| OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| I REASSESSED THE VALUE AT $533,244.84 USING THE |
| INTERNATIONAL CODE CONGRESS BUILDING VALUE DATED |
| PUBLISHED 02/14. |
| |
| NOTE: FLOOD ZONE REVIEW IS PENDING. |
| |
| STEVEN KENNEDY, CBO |
| CHIEF PLANS EXAMINER |
| (561) 805-6710 |
| [email protected] |
| |
| |
| |
| |
| |
| |