Plan Review Notes
Plan Review Notes For Permit 14050268
Permit Number 14050268
Review Stop B
Sequence Number 1
Notes
Date Text
2014-05-17 10:19:43***PROVISO***
 ***ISSUED AT CONTRACTOR'S RISK****
  
 FBC R310, FBC EB 604.1. FOR SLEEPING ROOM WINDOWS, THE
 CLEAR EMERGENCY ESCAPE AND RESCUE OPENING CANNOT BE
 REDUCED BY MORE THAN 5%.
  
 38" HIGH WINDOWS ARE SHOWN ON THE FLOOR PLAN. IF ANY OF
 THE 38" HIGH WINDOWS ARE LOCATED IN SLEEPING ROOMS,
 SUBMIT A REVISION WITH CALCULATIONS TO SHOW THAT THE
 CLEAR OPENING IS NOT REDUCED BY MORE THAN 5%.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved