2014-05-07 13:08:45BUILDING PLAN REVIEW
 REVISION: 14050190
 PERMIT: 13120825
 ADD: 5731 PREMIER PARK DR
 CONT: ZIRLBACH
 TEL: (941)539-4756
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 07/2014
 ACTION: DENIED
  
 1) SHEET P1.1PLUMBING DENIED:
 2010 FL ACCESSIBILITY CODE 211 DRINKING FOUNTAINS
 NO SPECIFICATIONS PROVIDED:
 211.3 MORE THAN MINIMUM NUMBER.
 WHERE MORE THAN THE MINIMUM NUMBER OF DRINKING
 FOUNTAINS SPECIFIED IN 211.2 ARE PROVIDED, 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.1 THROUGH 602.6, AND 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.7.
 EXCEPTION: WHERE 50 PERCENT OF THE DRINKING FOUNTAINS
 YIELDS A FRACTION, 50 PERCENT SHALL BE PERMITTED TO BE
 ROUNDED UP OR DOWN PROVIDED THAT THE TOTAL NUMBER OF
 DRINKING FOUNTAINS COMPLYING WITH 211 EQUALS 100
 PERCENT OF DRINKING FOUNTAINS.
  
 2) THE NEW ELECTRIC WATER FOUNTAIN DOES NOT PROVIDE
 WHERE IT WILL TIE INTO THE SANITARY AND WHERE THE VENT
 WILL BE LOCATED. 2010
 FBC-P TABLE 709.1 DRAINAGE FIXTURE UNITS & 908.1.
  