2014-05-07 13:08:45 | BUILDING PLAN REVIEW |
| REVISION: 14050190 |
| PERMIT: 13120825 |
| ADD: 5731 PREMIER PARK DR |
| CONT: ZIRLBACH |
| TEL: (941)539-4756 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. MAY 07/2014 |
| ACTION: DENIED |
| |
| 1) SHEET P1.1PLUMBING DENIED: |
| 2010 FL ACCESSIBILITY CODE 211 DRINKING FOUNTAINS |
| NO SPECIFICATIONS PROVIDED: |
| 211.3 MORE THAN MINIMUM NUMBER. |
| WHERE MORE THAN THE MINIMUM NUMBER OF DRINKING |
| FOUNTAINS SPECIFIED IN 211.2 ARE PROVIDED, 50 PERCENT |
| OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED |
| SHALL COMPLY WITH 602.1 THROUGH 602.6, AND 50 PERCENT |
| OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED |
| SHALL COMPLY WITH 602.7. |
| EXCEPTION: WHERE 50 PERCENT OF THE DRINKING FOUNTAINS |
| YIELDS A FRACTION, 50 PERCENT SHALL BE PERMITTED TO BE |
| ROUNDED UP OR DOWN PROVIDED THAT THE TOTAL NUMBER OF |
| DRINKING FOUNTAINS COMPLYING WITH 211 EQUALS 100 |
| PERCENT OF DRINKING FOUNTAINS. |
| |
| 2) THE NEW ELECTRIC WATER FOUNTAIN DOES NOT PROVIDE |
| WHERE IT WILL TIE INTO THE SANITARY AND WHERE THE VENT |
| WILL BE LOCATED. 2010 |
| FBC-P TABLE 709.1 DRAINAGE FIXTURE UNITS & 908.1. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |