Plan Review Notes For Permit 14050175 |
Permit Number |
14050175 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-06-09 13:09:29 | 6/9/14. | | PROJECT: PAPER SOURCE SHELL CONTRACT. | | PERMIT: 14050175 | | CODE: 2008 EDITION OF THE NEC AND THE 2010 EDITION OF | | THE FBC | | ACTION: DENIED | | | | COMMENTS: | | | | 1) PANEL SCHEDULE FOR PANEL A NOT SHOWN ON PLANS. | | PLEASE PROVIDE FBC 107.2.1 | | | | 2) RISER DIAGRAM REQUIRED BUT NOT SHOWN. PROVIDE A | | COMPLETE RISER DIAGRAM TO IDENTIFY PANELS, ASSOCIATED | | CIRCUITRY AND HOW THEY ARE BEING FED. PLEASE INDICATE | | ALL SPECIFIC PIPE AND WIRE TYPES AND SIZES. FBC | | 107.2.1. | | | | 3) IDENTIFY ELECTRICAL COMPONENTS ON FLOOR PLAN. | | IDENTIFY SQUARE SYMBOL AT REAR OF SPACE NEXT TO PANELS. | | THERE APEARS TO BE TWO DISCONNECTS ASSOCIATED WITH THIS | | EQUIPMENT. IDENTIFY EQUIPMENT AND CIRCUITRY ASSOCIATED | | WITH THESE DISCONNECTS ON THE FLOOOR PLAND AND ON THE | | RISRE, FBC 107.2.1 | | | | 4) FIRE ALARM DEVICES SHOWN ON PLANS. PLEASE EITHER | | INCLUDE SHOP DRAWINGS AND EQUIPMENT SUBMITTALS WITH | | SEPARATE PERMIT APPLICATION FOR FIRE ALARM OR INDICATE | | ON PLANS THE THESE ARE EITHER EXISTING DEVICES OR WILL | | BE APPLIED FOR AND INSTALLED UNDER SEPARATE PERMIT AT A | | LATER DATE. | | | | |
|