Plan Review Notes
Plan Review Notes For Permit 14050175
Permit Number 14050175
Review Stop E
Sequence Number 1
Notes
Date Text
2014-06-09 13:09:296/9/14.
 PROJECT: PAPER SOURCE SHELL CONTRACT.
 PERMIT: 14050175
 CODE: 2008 EDITION OF THE NEC AND THE 2010 EDITION OF
 THE FBC
 ACTION: DENIED
  
 COMMENTS:
  
 1) PANEL SCHEDULE FOR PANEL A NOT SHOWN ON PLANS.
 PLEASE PROVIDE FBC 107.2.1
  
 2) RISER DIAGRAM REQUIRED BUT NOT SHOWN. PROVIDE A
 COMPLETE RISER DIAGRAM TO IDENTIFY PANELS, ASSOCIATED
 CIRCUITRY AND HOW THEY ARE BEING FED. PLEASE INDICATE
 ALL SPECIFIC PIPE AND WIRE TYPES AND SIZES. FBC
 107.2.1.
  
 3) IDENTIFY ELECTRICAL COMPONENTS ON FLOOR PLAN.
 IDENTIFY SQUARE SYMBOL AT REAR OF SPACE NEXT TO PANELS.
 THERE APEARS TO BE TWO DISCONNECTS ASSOCIATED WITH THIS
 EQUIPMENT. IDENTIFY EQUIPMENT AND CIRCUITRY ASSOCIATED
 WITH THESE DISCONNECTS ON THE FLOOOR PLAND AND ON THE
 RISRE, FBC 107.2.1
  
 4) FIRE ALARM DEVICES SHOWN ON PLANS. PLEASE EITHER
 INCLUDE SHOP DRAWINGS AND EQUIPMENT SUBMITTALS WITH
 SEPARATE PERMIT APPLICATION FOR FIRE ALARM OR INDICATE
 ON PLANS THE THESE ARE EITHER EXISTING DEVICES OR WILL
 BE APPLIED FOR AND INSTALLED UNDER SEPARATE PERMIT AT A
 LATER DATE.
  
  