2014-07-03 07:01:29 | PLUMBING PLAN REVIEW |
| PERMIT: 14050167 |
| ADD: 400 N FLAGLER DR # PH-D2 |
| CONT: MARYJULI CONSTRUCTION |
| TEL: (561)386-6032 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: THURS. JULY 03/ 2014 |
| ACTION: DENIED |
| |
| 1) SHEET # 3 THE GUEST BATH # 2 SHOWS A ISOMETRIC OF |
| THE SANITARY, AS DRAWN WITH THE FIXTURE DRAINS ALL |
| DRAINING INTO THE STACK. PLEASE NOTE THIS TYPE FITTING |
| IS CALLED A COTTAGE TEE USED STRICKLY IN A R3 |
| RESIDENCE, EVEN THEN THE FIXTURES NEED TO BE VENTED, |
| NOTE THIS PLAN DOES NOT SHOW VENTING FOR THE WATER |
| CLOSET OR SHOWER. NOTE THIS IS A 3 PIPE DRAINAGE AND |
| VENT PIPE SYSTEM, NOT A WASTE STACK VENT(GUT STACK) NOR |
| IS THIS A ENGINEERED SOVENT SYSTEM. |
| |
| 2) IN THE MASTER BATH THE PLANS INDICATE THE ROTATING |
| OF THE WATERCLOSET, HOW WILL THE SANITARY PIPE BE MOVED |
| IN THE FLOOR, HOW WILL THE FIRE RATING OF THE FLOOR BE |
| PRESERVED. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 2010 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. 2010 FBC-P 307.3 |
| PENETRATIONS OF FLOOR/CEILING ASSEMBLIES AND |
| FIRE-RESISTANCE-RATED ASSEMBLIES. PENETRATIONS OF |
| FLOOR/CEILING ASSEMBLIES AND ASSEMBLIES REQUIRED TO |
| HAVE A FIRE-RESISTANCE RATING SHALL BE PROTECTED IN |
| ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 3) COMPLIED. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |