2014-07-25 11:55:16 | RESIDENTIAL (R2) ALTERATION, MECHANICAL REVIEW | | COMMENTS. | | CODE: 2010 FBC | | | | 1- THERE IS NO INFORMATION SUBMITTED SHOWING COMPLIANCE | | WITH THE BALANCED RETURN AIR SEC. 601.4 OF 2010 | | FBC-MECHANICAL. PROVIDE INFORMATION SHOWING COMPLIANCE | | WITH THE BALANCED RETURN AIR IN ALL HABITABLE ROOMS. | | | | 2- A) DUCT SIZE FEEDING THE MASTER BEDROOM, SITTING | | ROOM AND BEDROOM #2 WAS DOWN SIZED TO 28 X 4 AND 16 X 4 | | RESPECTIVELY. PROVIDE CALCULATIONS SHOWING COMPLIANCE | | WITH SEC. 603.2 OF 2010 FBC-MECHANICAL FOR THE PROPOSED | | DUCT SIZE. | | | | B) SIZE OF REGISTERS SUPPLYING AIR TO THE MASTER | | BEDROOM, SITTING ROOM AND BEDROOM #2 ARE BIGGER THAN | | THE DUCT FEEDING THEM. PROVIDE COMPLETE DETAILS AND | | SPECIFICATIONS SHOWING SUCH INSTALLATION. SEC. | | 107.2.1.3 CITY AMENDMENTS TO FBC. ALSO, COORDINATE WITH | | ITEM #2(A) ABOVE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|