Plan Review Notes
Plan Review Notes For Permit 14050167
Permit Number 14050167
Review Stop E
Sequence Number 2
Notes
Date Text
2014-07-10 09:03:32DATE: 7/9/2014
 PROJECT: WALDMAN APT.
 PERMIT#: 14050167
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) IN KITCHENS, PANTRIES, BREAKFAST ROOMS, DINING
 ROOMS, AND SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE
 OUTLETS FOR COUNTERTOP SPACES SHALL BE INSTALLED IN
 ACCORDANCE WITH NEC 210.52(C)(1) THROUGH (C)(5). THE
 PLANS DO NOT SHOW THE LOCATIONS OF ANY RECEPTACLE
 OUTLETS REVISE PLANS TO TO SHOW LOCATIONS OF ALL NEW
 OUTLETS INCLUDING ANY ADDITIONAL OUTLETS REQUIRED FOR
 COMPLIANCE IN ACCORDANCE WITH NEC 210.52(C)(1) THROUGH
 (C)(5).
  
 2) RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT
 ALONG THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. NEC 210.52 (A)(2).THE PLANS DO NOT
 SHOW THE LOCATIONS OF ANY RECEPTACLE OUTLETS EXCEPT FOR
 SOME REQUIRED FOR NEW MOTORIZED BLINDS.. REVISE PLANS
 TO TO SHOW LOCATIONS OF ALL NEW OUTLETS INCLUDING ANY
 ADDITIONAL OUTLETS REQUIRED FOR COMPLIANCE IN
 ACCORDANCE WITH NEC 210.52 (A)(2)
  
 3) PROVIDE PRODUCT APPROVALS AND INSTALLATION DETAILS
 FOR MOTORIZED BLINDS. LISTING AND LABELING REQUIRED BY
 AN APPROVED TESTING LAB. IN JUDGING EQUIPMENT,
 CONSIDERATION SUCH AS THE FOLLOWING SHALL BE EVALUATED:
 SUITABILITY OF EQUIPMENT MAY BE EVIDENCED BY LISTING OR
 LABELING. SUITABILITY FOR INSTALLATION AND USE IN
 CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC
 110.3(A)(1 THRU 8) LISTED OR LABELED EQUIPMENT SHALL BE
 INSTALLED AND USED IN ACCORDANCE WITH ANY INSTRUCTIONS
 INCLUDED IN THE LISTING AND LABELING. NEC 110.3(B)
  
 4) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF NEC 410.16(A) AND
 (B). REVISE PLANS TO INDICATE COMPLIANCE.
  
 5) METAL FRAMING MEMBERS SHALL BE BONDED TO THE
 EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY
 ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH
 THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION,
 A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING
 SHALL BE PERMITTED. FBC CHAPTER 27 SECTION 2704. REVISE
 PLANS TO INDICATE COMPLIANCE.
  
 6) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL
 NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT
 DISCONNECTING MEANS. NEC 210.63 SEE ALSO 210.8(A)(3),
 AND 406.8(B)(1). REVISE PLANS TO INDICATE COMPLIANCE.
  
 7) INDICATE DISCONNECTS WHERE REQUIRED AT A/C EQUIPMENT
 ETC.. NEC 440.14. REVISE PLANS TO INDICATE COMPLIANCE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]