Plan Review Notes
Plan Review Notes For Permit 14050167
Permit Number 14050167
Review Stop P
Sequence Number 1
Notes
Date Text
2014-05-28 06:21:56PLUMBING PLAN REVIEW
 PERMIT: 14050167
 ADD: 400 N FLAGLER DR # PH-D2
 CONT: MARYJULI CONSTRUCTION
 TEL: (561)386-6032
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 27/ 2014
 ACTION: DENIED
  
 1) THERE HAVE BEEN NO PLUMBING SHEETS PROVIDED, THE
 GUEST BATH # 2 PLEASE SHOW THE LOCATION OF THE VENT FOR
 THE NEWLY PLACED VANITY, DISTANCE FROM TRAP TO VENT,
 2010 FBC-P TABLE 906.1.
  
 2) IN THE MASTER BATH THE PLANS INDICATE THE ROTATING
 OF THE WATERCLOSET, HOW WILL THE SANITARY PIPE BE MOVED
 IN THE FLOOR, HOW WILL THE FIRE RATING OF THE FLOOR BE
 PRESERVED.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED. 2010 FBC-P 307.3
 PENETRATIONS OF FLOOR/CEILING ASSEMBLIES AND
 FIRE-RESISTANCE-RATED ASSEMBLIES. PENETRATIONS OF
 FLOOR/CEILING ASSEMBLIES AND ASSEMBLIES REQUIRED TO
 HAVE A FIRE-RESISTANCE RATING SHALL BE PROTECTED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
  
 3) PLEASE PROVIDE THE VENT LOCATION OF THE KITCHEN SINK
 AND THE DITANCE FROM THE TRAP 2010 FBC-P TABLE 906.1.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  