Plan Review Notes For Permit 14050167 |
Permit Number |
14050167 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-06-02 17:39:20 | 400 N. FLAGLER DR. PH-D2 | | | | ELECTRICAL 1ST REVIEW | | | | ACTION: DENIED. | | | | CODE REFERENCED: 2008 EDITION OF THE NEC AND THE 2010 | | EDITION OF THE FLORIDA BUILDING CODE. | | | | 1) PROVIDE A LOAD CALCULATION. CIRCUITS HAVE BEEN | | ADDED. THIS AFFECTS THE TOTAL CONNECTED LOAD. THE PLAN | | INDICATES THE PANEL WILL BE CHANGED BUT NOT THE FEEDER. | | FBC 107.2.1 | | | | 2) PROVIDE AN EXISTING RISER DIAGRAM INDICATING THE | | EXISTING FEEDER TO THE NEW PANEL. PROVIDE WIRE TYPE AND | | SIZE. FBC 107.2.1 | | | | 3) IN KITCHENS, PANTRIES, BREAKFAST ROOMS, DINING | | ROOMS, AND SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE | | OUTLETS FOR COUNTERTOP SPACES SHALL BE INSTALLED IN | | ACCORDANCE WITH NEC 210.52(C)(1) THROUGH (C)(5). | | | | 4) RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT | | ALONG THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A | | RECEPTACLE OUTLET. NEC 210.52 (A)(2). | | | | 5) THE FLOOR PLAN SHALL INDICATE REQUIRED LIGHTING | | OUTLETS PER THE NEC 210.70 | | | | 6) RECESSED LIGHTING TO BE AIR TIGHT AND IC RATED. AT | | LEAST 50% OF THE LAMPS IN PERMANENTLY INSTALLED LIGHT | | FIXTURES SHALL BE HIGH EFFICIENCY. FBC-R 402.4.5, & | | 404.1 | | | | 7) PROVIDE CUT SHEETS ON RECESSED LIGHTS TO INDICATE | | COMPLIANCE WITH THE NEC 110.3 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421. | | 561-805-6717 OR [email protected] |
|