2014-06-02 17:39:20400 N. FLAGLER DR. PH-D2
  
 ELECTRICAL 1ST REVIEW
  
 ACTION: DENIED.
  
 CODE REFERENCED: 2008 EDITION OF THE NEC AND THE 2010
 EDITION OF THE FLORIDA BUILDING CODE.
  
 1) PROVIDE A LOAD CALCULATION. CIRCUITS HAVE BEEN
 ADDED. THIS AFFECTS THE TOTAL CONNECTED LOAD. THE PLAN
 INDICATES THE PANEL WILL BE CHANGED BUT NOT THE FEEDER.
 FBC 107.2.1
  
 2) PROVIDE AN EXISTING RISER DIAGRAM INDICATING THE
 EXISTING FEEDER TO THE NEW PANEL. PROVIDE WIRE TYPE AND
 SIZE. FBC 107.2.1
  
 3) IN KITCHENS, PANTRIES, BREAKFAST ROOMS, DINING
 ROOMS, AND SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE
 OUTLETS FOR COUNTERTOP SPACES SHALL BE INSTALLED IN
 ACCORDANCE WITH NEC 210.52(C)(1) THROUGH (C)(5).
  
 4) RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT
 ALONG THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. NEC 210.52 (A)(2).
  
 5) THE FLOOR PLAN SHALL INDICATE REQUIRED LIGHTING
 OUTLETS PER THE NEC 210.70
  
 6) RECESSED LIGHTING TO BE AIR TIGHT AND IC RATED. AT
 LEAST 50% OF THE LAMPS IN PERMANENTLY INSTALLED LIGHT
 FIXTURES SHALL BE HIGH EFFICIENCY. FBC-R 402.4.5, &
 404.1
  
 7) PROVIDE CUT SHEETS ON RECESSED LIGHTS TO INDICATE
 COMPLIANCE WITH THE NEC 110.3
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.