Plan Review Notes For Permit 14050131 |
Permit Number |
14050131 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-05-06 11:37:03 | ISSUED WITH THE FOLLOWING PROVISO: | | | | 1) 2010 FBC 402.4.5 RECESSED LIGHTS. REQUIRES THAT | | RECESSED LUMINAIRES BE SEALED, AIR TIGHT, IC RATED AND | | LABELED AS MEETING ASTME 283. PLEASE PROVIDE CUT SHEETS | | ON THE PROPOSED FIXTURES INDICATING COMPLIANCE WITH | | THIS ARTICLE. | | | | 2) 2008 NEC 110.3 REQUIRES THAT EQUIPMENT BE LISTED AND | | LABELED FOR THEIR INTENDED USE. PLEASE PROVIDE CUT | | SHEETS INDICATING COMPLIANCE WITH THIS ARTICLE FOR | | FIXTURES AND HYDRO MASSAGE TUB. | | | | 3) 2008 NEC 680 PART VII HYDRO MASSAGE BATHTUBS AS | | DEFINED IN 680.2 REQUIRES COMPLIANCE WITH PART VII OF | | THIS ARTICLE. PLEASE PROVIDE CUT SHEETS ON THE HYDRO | | MASSAGE TUB AND NOTATIONS ON THE PLANS INDICATING | | COMPLIANCE WITH THIS ARTICLE. | | | | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. | | I CAN BE REACHED AT 561-805-6717 OR [email protected]. | | THANK YOU | | |
|