Plan Review Notes
Plan Review Notes For Permit 14050113
Permit Number 14050113
Review Stop B
Sequence Number 1
Notes
Date Text
2014-05-05 15:00:272010 FBC
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVAL FOR THE CERTAINTEED MODIFIED
 BITUMEN ROOFING NOA NO. 13-0204.03 HAS BEEN SUPERSEDED
 BY NOA NO. 14-0224.03. PLEASE SUBMIT TWO COPIES OF THE
 CURRENT NOA. DCA RULE 9N-3
  
 2) THE STRUCTURE IS LOCATED IN A 170 MPH VULT WIND
 SPEED AND HAS AN EXPOSURE CATEGORY C. THE MAXIMUM
 DESIGN PRESSURE IN THE NOA FOR THE SPECIFIED SYSTEM ON
 PAGE 28 IS -52.5 PSF. THIS PRESSURE IS TOO LOW FOR THE
 PERIMETER AND CORNER ROOF AREAS. SUBMIT TO SETS OF
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING IN THESE AREAS AS REQUIRED BY LIMITATION
 NUMBER 7 OF THE NOA. FBC R301.2.1
  
 3) SPECIFY THE SEPARATE SQFT AREA OF THE SLOPED AND
 FLAT ROOF AREAS. CITY AMENDMENTS 107.2.1 AND 109.3
  
 4) VALUE OF WORK OF $8000 ON APPLICATION IS LOW. VALUE
 WAS INCREASED FROM $8,000 TO $10,600 BASED ON MARSHALL
 AND SWIFT VALUATION GUIDE. CITY AMENDMENTS 109.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW