2014-09-03 16:05:408100 (8225) IBIS BOULEVARD
 PERMIT #14050097
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FOR THE ORIGINAL COMMENTS (X3) I OFFER THE FOLLOWING
 RESPONSE AND POSSIBLE SOLUTION:
 A MONUMENTAL STAIR/CONVENIENCE OPENING IS REQUIRED TO
 BE SEPARATED FROM CORRIDORS ON EITHER FLOOR LEVEL PER
 SECTION 8.6.8.2(3). THE OPENING IS NOT SEPARATED FROM
 THE CORRIDORS (GALLERY #224 & #252). ADDITIONALLY, EXIT
 SIGNAGE HAS BEEN ADDED IN ELEVATOR LOBBY #104 ROUTING
 OCCUPANTS THROUGH THE CONVENIENCE OPENING, PASSED THE
 OPEN STAIR, INTO A MERCANTILE OCCUPANCY (GOLF SHOP).
 PER SECTION 8.6.8.2(5), OPENINGS ARE NOT PERMITTED BE
 PART OF THE MEANS OF EGRESS (IN THIS CASE EXIT ACCESS).
 WHILE OCCUPANTS DO NOT NEED TO TRAVERSE THE OPEN STAIR
 FOR EGRESS PURPOSES, THEY WILL, ESPECIALLY WHEN FACED
 WITH A STRESSFUL SITUATION. SINCE THIS STAIR IS OPEN ON
 TOP AND ENCLOSED ON BOTTOM, A FIRE SITUATION COULD
 RESULT IN "COLD SMOKE" ACCUMULATION IN THIS STAIR...THE
 SAME STAIR OCCUPANTS ARE BEING DIRECTED TO FOR EXIT
 ACCESS. NO DOOR TAG PROVIDED FOR DOUBLE EXIT ACCESS
 DOORS LOCATED BETWEEN MONUMENTAL STAIR #111 AND GOLF
 SHOP. PROVIDING EXIT ACCESS THROUGH THESE DOORS WOULD
 APPEAR TO CAUSE A CONFLICT WITH TRYING TO SECURE/LOCK
 THESE DOORS FROM THE GOLF SHOP SIDE TO PREVENT THEFT.
  
 A POSSIBLE SOLUTION WOULD BE TO RELOCATE THE BOTTOM
 STAIR ENCLOSURE AND DOOR TO COLUMN INTERSECTION
 F/10-11. THIS WAY THE OPENING WOULD BE SEPARATED FROM
 THE CORRIDOR, AND OCCUPANTS WOULDN'T GET ENTICED INTO
 USING THE OPEN STAIR FOR EGRESS. THE ONLY ISSUE WOULD
 BE INSTALLING PASSAGE DOOR HARDWARE ON THE EXIT ACCESS
 DOORS LEADING THROUGH THE GOLF SHOP.
  
 ORIGINAL COMMENTS:
 SHEET AE104: MONUMENTAL STAIR #209 APPEARS TO BE
 FUNCTIONING AS A "CONVENIENCE OPENING" PER NFPA 101
 SECTION 8.6.8; HOWEVER, REQUIREMENT #3 REQUIRES THAT
 SUCH OPENINGS SHALL BE SEPARATED FROM CORRIDORS.
  
 SHEET AE101: CULTURAL CLASS #125 (71 PERSONS) HAS TWO
 EXIT ACCESS DOORS THAT HAVE APPROPRIATE SEPARATION;
 HOWEVER, BOTH DOORS LEAD TO THE SAME CORRIDOR GALLERY
 #102 WHEREBY ONE FIRE EVENT COULD COMPROMISE BOTH
 DOORS. PER SECTION 12.2.5.1.2 THE COMMON PATH OF TRAVEL
 IS LIMITED TO 75 FEET FOR 50 OR LESS OCCUPANTS AND 20
 FEET FOR 51 OR MORE OCCUPANTS. THE EXIT ACCESS DOORS
 SHALL BE ARRANGED FOR OCCUPANTS TO HAVE ACCESS TO AT
 LEAST TWO EXITS BY SEPARATE WAYS OF TRAVEL PER SECTION
 7.5.1.1.1.
  
 SHEET AE101: LOUNGE #110 THE COMMON PATH OF TRAVEL IS
 135 FEET. PER SECTION 12.2.5.1.2 THE COMMON PATH OF
 TRAVEL IS LIMITED TO 75 FEET FOR 50 OR LESS OCCUPANTS
 AND 20 FEET FOR 51 OR MORE OCCUPANTS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730