2014-09-22 10:38:53 | DATE: 9/22/2014 |
| PROJECT: IBIS |
| PERMIT#: 14050097 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 3RD ELECTRICAL PLAN REVIEW |
| ACTION: PROVISO |
| |
| 1) SHEET EL103 |
| TERRACE AND STAIRS. LIGHTING CONTROL REQUIRED FOR |
| EXTERIOR LIGHTING. FBC 505.2.4 |
| |
| 2) SHEET EP104 |
| 214-BAR TERRACE. FLUSH CEILING OUTLETS TO HAVE GFCI |
| PROTECTION. |
| 212-BAR LOUNGE. PROVIDE MANUFACTURER?S PRODUCT |
| SPECIFICATIONS ON FLOOR BOXES. FLOOR BOXES SHALL BE |
| APPROVED TO MAINTAIN THE FIRE RATED INTEGRITY OF THE |
| FLOOR. |
| |
| 3) SHEET EP401 |
| 207- STORAGE RM. THIS IS ELECTRICAL EQUIPMENT ROOM. |
| THERE SHALL BE NO STORAGE ALLOWED AND SHALL BE |
| IDENTIFIED WITH A SIGN STATING ?ELECTRIC ROOM. NO |
| STORAGE ALLOWED? MAINTAIN WORKING CLEARANCE AND |
| DEDICATED WORKING SPACE. NEC 110.26 |
| |
| 4) SHEET EP501 |
| A) INDICATE HOW THE CLUBHOUSE GROUNDING ELECTRODE |
| SYSTEM TIES TO MDP BARN GROUNDING ELECTRODE SYSTEM. |
| NOTE 3 THIS SHEET STATES TO BOND PANEL IT1 GROUND TO |
| CLUBHOUSE GROUNDING ELECTRODE SYSTEM. THIS WOULD CREATE |
| A DIFFERENCE OF POTENTIAL BETWEEN THE BARN AND |
| CLUBHOUSE SYSTEMS. |
| B) THE ATS AT THE NEW GENERATOR IS IDENTIFIED AS A |
| 4POLE ATS. I BELIEVE THIS IS MIS-LABELED AND THE INTENT |
| IS FOR A STANDARD 3 POSITION ATS WITH A SOLID NEUTRAL |
| FOR STANDARD OPTIONAL STANDBY SYSTEM AS ALSO NOTED THIS |
| SHEET. |
| |
| 5) SHEET ES101 |
| SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| ARE REQUIRED FOR SITE LIGHTING, GENERATOR, FIRE ALARM, |
| SECURITY, CCTV, NETWORK, DATA/COM, AUDIO, VIDEO, AND |
| SIGNAGE. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |