2014-09-22 10:38:53DATE: 9/22/2014
 PROJECT: IBIS
 PERMIT#: 14050097
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) SHEET EL103
 TERRACE AND STAIRS. LIGHTING CONTROL REQUIRED FOR
 EXTERIOR LIGHTING. FBC 505.2.4
  
 2) SHEET EP104
 214-BAR TERRACE. FLUSH CEILING OUTLETS TO HAVE GFCI
 PROTECTION.
 212-BAR LOUNGE. PROVIDE MANUFACTURER?S PRODUCT
 SPECIFICATIONS ON FLOOR BOXES. FLOOR BOXES SHALL BE
 APPROVED TO MAINTAIN THE FIRE RATED INTEGRITY OF THE
 FLOOR.
  
 3) SHEET EP401
 207- STORAGE RM. THIS IS ELECTRICAL EQUIPMENT ROOM.
 THERE SHALL BE NO STORAGE ALLOWED AND SHALL BE
 IDENTIFIED WITH A SIGN STATING ?ELECTRIC ROOM. NO
 STORAGE ALLOWED? MAINTAIN WORKING CLEARANCE AND
 DEDICATED WORKING SPACE. NEC 110.26
  
 4) SHEET EP501
 A) INDICATE HOW THE CLUBHOUSE GROUNDING ELECTRODE
 SYSTEM TIES TO MDP BARN GROUNDING ELECTRODE SYSTEM.
 NOTE 3 THIS SHEET STATES TO BOND PANEL IT1 GROUND TO
 CLUBHOUSE GROUNDING ELECTRODE SYSTEM. THIS WOULD CREATE
 A DIFFERENCE OF POTENTIAL BETWEEN THE BARN AND
 CLUBHOUSE SYSTEMS.
 B) THE ATS AT THE NEW GENERATOR IS IDENTIFIED AS A
 4POLE ATS. I BELIEVE THIS IS MIS-LABELED AND THE INTENT
 IS FOR A STANDARD 3 POSITION ATS WITH A SOLID NEUTRAL
 FOR STANDARD OPTIONAL STANDBY SYSTEM AS ALSO NOTED THIS
 SHEET.
  
 5) SHEET ES101
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATOR, FIRE ALARM,
 SECURITY, CCTV, NETWORK, DATA/COM, AUDIO, VIDEO, AND
 SIGNAGE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]