2014-08-25 12:18:18 | BUILDING PLAN REVIEW |
| PERMIT: 14050097 |
| ADD: 8100 IBIS BLVD |
| CONT:THE WEITZ CO. |
| TEL: (561)686-5511 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 3RD REVIEW |
| DATE: MON. AUG.25/ 2014 |
| ACTION: DENIED |
| |
| 1) COMPLIED. |
| |
| 1A) COMPLIED. |
| |
| 1B) 3RD REQUEST. SEMI-COMPLIED. G1-101 DINING ROOM 131 |
| INDICATES A OCCUPANCY LOAD OF 67 TRAVELING THROUGH THE |
| EXTERIOR DOUBLE DOORS. WHEN FIGURING THE OCCUPANCY LOAD |
| AT 15 SQ FT / OCC WITHOUT THE BAR THE LOAD IS APPROX. |
| 60 OCCUPANTS WHICH WILL REQUIRE A 2ND EXIT. 2010 FBC-B |
| 1008.1.2. |
| THE PLANS NOW SHOW THE 2ND MEANS OF EGRESS THROUGH THE |
| DINING ROOM # 130 INTO VESTIBULE 127 AND A TWO WAY EXIT |
| DIRECTIONAL INTO CORRIDOR 128 WHICH LEADS BACK TO THE |
| FRONT ENTRY. THERE IS NO REMOTNESS BETWEEN THE (2) |
| FRONT ENTRY DOORS. |
| |
| THE OTHER ISSUE IS WHERE THE VESTIBULE 127 LEADS YOU TO |
| CORRIDOR # 128 WITH THE DOUBLE DIRECTIONAL SIGN IF YOU |
| MAKE A RIGHT HAND TURN THERE IS A OCCUPANT LOAD |
| DIRECTIONAL ARROW (OCC LOAD 48) POINTING TO THE FRONT |
| OF THE BUILDING IF THIS WAS A DOUBLE ARROWED ALLOWING |
| THE OCCUPANTS FROM THE VESTIBULE TO TRAVEL UP CORRIDOR |
| 128 MAKE A LEFT INTO COORIDOR 190 WHICH DOES GO TO THE |
| EXTERIOR OF THE BUILDING. YOU WOULD HAVE TO STILL MEET |
| THE MAXIMUM TRAVEL DISTANCE OF 250 FT. IF BOTH OF THE |
| FRONT ENTRY WERE LOST BECAUSE OF FIRE YOU WOULD STILL |
| BE ABLE TO USE THIS OTHER EXIT. 1015.2.2 THREE OR MORE |
| EXIT ACCESS DOORWAYS. |
| |
| 1C) COMPLIED. |
| |
| 1D) 3RD REQUEST. IN BOTH THE CULTURAL CLASS # 125 & THE |
| TRAINING ROOM # 169 ARE BOTH TAKEN AT 20 SQ FT/ OCC. |
| THE 20 SQ FT IS TAKEN WITH AN EDUCATIONAL SETTING |
| KINDERGADEN -12TH GRADE. FOR ADULT EDUCATION IN |
| COLLEGES IT IS CONSIDERED BUSINESS OCCUPANCY. THIS IS A |
| MULTI-PURPOSE ROOM WHERE AN ASSEMBLY OCCUPANCY CAN BE |
| TAKEN AT 15 SQ FT/ OCCUPANT. 2010 FBC-B TABLE 1004.1.1. |
| |
| WHERE ARE DIFFERENCES WITHIN THE CODES THE MORE |
| STRINGENT OF THE CODES WOULD BE WHAT WE USE. 2010 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, ADMINISTRATION, 102.1 GENERAL. WHERE, IN ANY |
| SPECIFIC CASE, DIFFERENT SECTIONS OF THIS CODE SPECIFY |
| DIFFERENT MATERIALS, METHODS OF CONSTRUCTION OR OTHER |
| REQUIREMENTS, THE MOST RESTRICTIVE SHALL GOVERN. WHERE |
| THERE IS A CONFLICT BETWEEN A GENERAL REQUIREMENT AND A |
| SPECIFIC REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| APPLICABLE. |
| |
| 2) SHEET AE105: |
| |
| 2A) COMPLIED. |
| |
| 2B) COMPLIED. 1016.1 EXC# 3. |
| |
| 3) COMPLIED, DO NOT COMBINE RESTROOMS FOR COUNT OF 6 OR |
| MORE. |
| |
| 4)COMPLIED. |
| |
| 5) COMPLIED, SPOKE WITH ENGINEER, SHOWED ME WHICH SHEET |
| THEY WERE LOCATED. |
| |
| |
| 6) 3RD REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| PLEASE BE AWARE WHEN GIVEN WRITTEN DOCUMENTATION WHEN |
| THE WIND PRESSURES ARE CORRECT, THE PRODUCT APPROVALS |
| CAN BE A DEFERRED SUBMITTAL 107.3.4.2. |
| |
| 7) 3RD REQUEST. CAN BE A DEFERRED SUBMITTAL 107.3.4.2. |
| 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 8) COMPLIED. |
| |
| 9) THANK YOU FOR NARRATIVE. |
| JAMES A. WITMER CBO |