Plan Review Notes
Plan Review Notes For Permit 14050097
Permit Number 14050097
Review Stop P
Sequence Number 2
Notes
Date Text
2014-08-01 06:49:02BUILDING PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 NOTICE TO DESIGNER OF RECORD. THERE WERE NO CHANGES
 MADE TO THE PLANS. THERE ARE NO REVISION NUMBERS ON ANY
 OF THE SHEETS INDICATING WHERE CORRCTIONS WERE MADE TO
 THE PLANS NOR THROUGH PROJECT DOX DOES VERSION 2 EXIT
 SHOWING CORRECTIONS WERE MADE.
  
 IGNORED!!! . A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 NOTICE TO THE DESIGNER OF RECORD!!!! CHAPTER
 553.80(2)(B) FLORIDA STATUTES STATES THAT A LOCAL
 GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE OR MORE TIMES
 FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
  
 2ND REVIEW
 DATE:FRI. AUG. 01/ 2014
 ACTION: DENIED
  
 NOTICE TO DESIGNER OF RECORD. THERE WERE NO CHANGES
 MADE TO THE PLANS. THERE ARE NO REVISION NUMBERS ON ANY
 OF THE SHEETS INDICATING WHERE CORRCTIONS WERE MADE TO
 THE PLANS NOR THROUGH PROJECT DOX DOES VERSION 2 EXIT
 SHOWING CORRECTIONS WERE MADE.
  
 IGNORED!!! WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 NOTICE TO THE DESIGNER OF RECORD!!!! CHAPTER
 553.80(2)(B) FLORIDA STATUTES STATES THAT A LOCAL
 GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE OR MORE TIMES
 FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
 1) 2ND REQUEST. SHEET P105 NOR 305 DOES NOT INDICATE
 THE SIZE OF THE VERTICAL CONDUCTORS AND LEADERS,
 BUILDING STORM DRAINS, BUILDING STORM SEWERS, AND ANY
 HORIZONTAL BRANCHES OF SUCH DRAINS OR SEWERS SHALL BE
 BASED ON THE 100-YEAR HOURLY RAINFALL RATE INDICATED IN
 FIGURE 1106.1 OR ON OTHER RAINFALL RATES DETERMINED
 FROM APPROVED LOCAL WEATHER DATA. 2010 FBC-P 1106.1.
  
 2) 2ND REQUEST. P105 DOES NOT PROVIDE WHAT AREA THE
 ROOF DRAINS ARE RECEIVING, IF THIS IS JUST THE FLAT
 AREA OR IF THIS AREA IS ALSO THE CONTRIBUTING SLOPED
 ARAES, PLEASE PROVIDE A BREAK OUT FOR EACH ROOF DRAIN
 SERVED OF FLAT AND ADJOINING SLOPED ROOFS THAT
 CONTRIBUTE TO THE ROOF DRAIN LOAD.
 2010 1106.4.
  
 3) 2ND REQUEST. SHEET P201 VERSES P301
 3A) THE LADIES RESTROOM 222 THE 4 WATER CLOSETS IN A
 ROW IS MISSING THE VENT CONNECTION FOR A CIRCUIT VENT
 SEE SECTION 2010 FBC-P 911.2.
  
 3B) 2ND REQUEST. IT APPEARS ONE OF THE WATER CLOSETS IN
 THE MENS RESTROOM IS NOT VENTEDAS A INDIVDUAL VENT OF
 THE BEGINNING OF A CIRCUIT VENT SEE 2010 FBC-P 907.1 &
 911.2. T
  
 3C) 2ND REQUEST. IT APPEARS ONE OF THE WATER CLOSETS IN
 THE MENS RESTROOM IS NOT VENTED AS A INDIVDUAL VENT OF
 THE BEGINNING OF A CIRCUIT VENT SEE 2010 FBC-P 907.1 &
 911.2. T
  
 4A) 2ND REQUEST. 0173-P304 RISER E GREASE WASTE, THE
 PLANS INDICATE THE GREASE WASTE FROM KITCHENS # 135 &
 #245, THE PLANS DO NOT COMMENT ON THE DRAINAGE FIXTURE
 UNITS FOR THE GREASE WASTE NOR MENTION SIZING NOR THE
 LOCATION OF THE GREASE INTERCEPTOR. 2010 FBC-PLUMBING
 1003.2. APPROVAL. 1003.3.3 SIZED. NOTE IF A CONCRETE
 VAULT TYPE OF INTERCEPTOR IS TO BE INSTALLED PLEASE
 NOTE THAT FBC-P TABLE 1003.5.1 IS THE SIZING TABLE TO
 BE USED FOR THIS TYPE OF APPLICATION.
  
 4B) 2ND REQUEST. THE PLANS DO NOT INDICATE IF ANY FOOD
 WASTE GRINDERS ARE GOING TO BE INSTALLED. 2010
 FBC-PLUMBING 1003.3.2.
  
 4C) 2ND REQUEST. THE ARCHITECTURAL SHEETS & STRURTURAL
 SHEETS BOTH INDICATE THE ELEVATOR PIT TO HAVE A SUMP
 PIT. PLANS ARE NOT CLEAR IF THIS IS TO BE A HYDROLIC
 ELEVATOR, IF SO PLEASE INDICATE HOW COMPLIANCE WITH
 2010 FBC-PLUMBING 1003.4 OIL SPEARATOR REQUIRED WILL BE
 ACHIEVED. I DID NOT SEE A DETAIL FOR A SUMP IN THE
 ELEVATOR PIT AND WASTE CONNECTIONS.SHEET P401 DOES
 INDICATE THE USE OF ZOELLER SUBMERSIBLE SUMP PUMP
 EXCEPTION: AN OIL SEPARATOR IS NOT REQUIRED IN
 HYDRAULIC ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM
 IS INSTALLED.
  
 1003.4.2 OIL SEPARATOR DESIGN.
 OIL SEPARATORS SHALL BE DESIGNED IN ACCORDANCE WITH
 SECTIONS 1003.4.2.1 AND 1003.4.2.2.
  
 1003.4.2.1 GENERAL DESIGN REQUIREMENTS.
 OIL SEPARATORS SHALL HAVE A DEPTH OF NOT LESS THAN 2
 FEET (610 MM) BELOW THE INVERT OF THE DISCHARGE DRAIN.
 THE OUTLET OPENING OF THE SEPARATOR SHALL HAVE NOT LESS
 THAN AN 18-INCH (457 MM) WATER SEAL.
  
 5) 2ND REQUEST. SHEET 0176- P401 PLUMBING SCHEDULE.
 TTRAP PRIMERS INDICATE PRECISION PLUMBING PRODUCTS BUT
 THE ACTUAL TYPE OR MODEL NUMBER IS NOT INDICATED NOR IS
 THE CONFORMANCE FOR TRAP SEAL PRIMER VALVES TO COMPLY
 WITH ASSE 1018 OR ASSE 1044. 2010 FBC-P 1002.4.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved