2014-08-01 07:01:41 | FUEL GAS PLAN REVIEW |
| PERMIT: 14050097 |
| ADD: 8100 IBIS BLVD |
| CONT:THE WEITZ CO. |
| TEL: (561)686-5511 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| |
| 3D REVIEW |
| DATE: MON. AUG. 25/ 2014 |
| ACTION: DENIED |
| |
| SHEET P306 GAS PIPING ISOMETRIC. |
| |
| GAS PERMIT APPLICATION REQUIREMENTS, MISSING |
| INFORMATION: |
| |
| |
| 1. COMPLIED. |
| |
| 2. COMPLIED. |
| |
| 3.. COMPLIED. |
| |
| 4. 3RD REQUEST. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE OUTLET IN THE |
| BUILDING AND/OR SYSTEM PER THE FBC-2010 FUEL GAS |
| APPENDIX A ? USE OF CAPACITY SECTION A.3.1(4) |
| |
| 2010 FBC- FUEL GAS |
| A.3.1 LONGEST LENGTH METHOD. |
| THIS SIZING METHOD IS CONSERVATIVE IN ITS APPROACH BY |
| APPLYING THE MAXIMUM OPERATING CONDITIONS IN THE SYSTEM |
| AS THE NORM FOR THE SYSTEM AND BY SETTING THE LENGTH OF |
| PIPE USED TO SIZE ANY GIVEN PART OF THE PIPING SYSTEM |
| TO THE MAXIMUM VALUE. |
| |
| TO DETERMINE THE SIZE OF EACH SECTION OF GAS PIPING IN |
| A SYSTEM WITHIN THE RANGE OF THE CAPACITY TABLES, |
| PROCEED AS FOLLOWS (ALSO SEE SAMPLE CALCULATIONS |
| INCLUDED IN THIS APPENDIX): |
| |
| (1) DIVIDE THE PIPING SYSTEM INTO APPROPRIATE SEGMENTS |
| CONSISTENT WITH THE PRESENCE OF TEES, BRANCH LINES AND |
| MAIN RUNS. FOR EACH SEGMENT, DETERMINE THE GAS LOAD |
| (ASSUMING ALL APPLIANCES OPERATE SIMULTANEOUSLY) AND |
| ITS OVERALL LENGTH. AN ALLOWANCE (IN EQUIVALENT LENGTH |
| OF PIPE) AS DETERMINED FROM TABLE A.2.2 SHALL BE |
| CONSIDERED FOR PIPING SEGMENTS THAT INCLUDE FOUR OR |
| MORE FITTINGS. |
| |
| (2) DETERMINE THE GAS DEMAND OF EACH APPLIANCE TO BE |
| ATTACHED TO THE PIPING SYSTEM. WHERE TABLES 402.4(1) |
| THROUGH 402.4(22) ARE TO BE USED TO SELECT THE PIPING |
| SIZE, CALCULATE THE GAS DEMAND IN TERMS OF CUBIC FEET |
| PER HOUR FOR EACH PIPING SYSTEM OUTLET . WHERE TABLES |
| 402.4(23) THROUGH 402.4(35) ARE TO BE USED TO SELECT |
| THE PIPING SIZE, CALCULATE THE GAS DEMAND IN TERMS OF |
| THOUSANDS OF BTU PER HOUR FOR EACH PIPING SYSTEM OUTLET |
| . |
| |
| (3) WHERE THE PIPING SYSTEM IS FOR USE WITH OTHER THAN |
| UNDILUTED LIQUEFIED PETROLEUM GASES, DETERMINE THE |
| DESIGN SYSTEM PRESSURE, THE ALLOWABLE LOSS IN PRESSURE |
| (PRESSURE DROP), AND SPECIFIC GRAVITY OF THE GAS TO BE |
| USED IN THE PIPING SYSTEM. |
| |
| (4) DETERMINE THE LENGTH OF PIPING FROM THE POINT OF |
| DELIVERY TO THE MOST REMOTE OUTLET IN THE |
| BUILDING/PIPING SYSTEM. |
| |
| |
| |
| 5. COMPLIED. |
| 6. COMPLIED. |
| |
| 7. COMPLIED. |
| |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |