Plan Review Notes
Plan Review Notes For Permit 14050097
Permit Number 14050097
Review Stop G
Sequence Number 2
Notes
Date Text
2014-08-01 07:01:41FUEL GAS PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
 3D REVIEW
 DATE: MON. AUG. 25/ 2014
 ACTION: DENIED
  
 SHEET P306 GAS PIPING ISOMETRIC.
  
 GAS PERMIT APPLICATION REQUIREMENTS, MISSING
 INFORMATION:
  
  
 1. COMPLIED.
  
 2. COMPLIED.
  
 3.. COMPLIED.
  
 4. 3RD REQUEST. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND/OR SYSTEM PER THE FBC-2010 FUEL GAS
 APPENDIX A ? USE OF CAPACITY SECTION A.3.1(4)
  
 2010 FBC- FUEL GAS
 A.3.1 LONGEST LENGTH METHOD.
 THIS SIZING METHOD IS CONSERVATIVE IN ITS APPROACH BY
 APPLYING THE MAXIMUM OPERATING CONDITIONS IN THE SYSTEM
 AS THE NORM FOR THE SYSTEM AND BY SETTING THE LENGTH OF
 PIPE USED TO SIZE ANY GIVEN PART OF THE PIPING SYSTEM
 TO THE MAXIMUM VALUE.
  
 TO DETERMINE THE SIZE OF EACH SECTION OF GAS PIPING IN
 A SYSTEM WITHIN THE RANGE OF THE CAPACITY TABLES,
 PROCEED AS FOLLOWS (ALSO SEE SAMPLE CALCULATIONS
 INCLUDED IN THIS APPENDIX):
  
 (1) DIVIDE THE PIPING SYSTEM INTO APPROPRIATE SEGMENTS
 CONSISTENT WITH THE PRESENCE OF TEES, BRANCH LINES AND
 MAIN RUNS. FOR EACH SEGMENT, DETERMINE THE GAS LOAD
 (ASSUMING ALL APPLIANCES OPERATE SIMULTANEOUSLY) AND
 ITS OVERALL LENGTH. AN ALLOWANCE (IN EQUIVALENT LENGTH
 OF PIPE) AS DETERMINED FROM TABLE A.2.2 SHALL BE
 CONSIDERED FOR PIPING SEGMENTS THAT INCLUDE FOUR OR
 MORE FITTINGS.
  
 (2) DETERMINE THE GAS DEMAND OF EACH APPLIANCE TO BE
 ATTACHED TO THE PIPING SYSTEM. WHERE TABLES 402.4(1)
 THROUGH 402.4(22) ARE TO BE USED TO SELECT THE PIPING
 SIZE, CALCULATE THE GAS DEMAND IN TERMS OF CUBIC FEET
 PER HOUR FOR EACH PIPING SYSTEM OUTLET . WHERE TABLES
 402.4(23) THROUGH 402.4(35) ARE TO BE USED TO SELECT
 THE PIPING SIZE, CALCULATE THE GAS DEMAND IN TERMS OF
 THOUSANDS OF BTU PER HOUR FOR EACH PIPING SYSTEM OUTLET
 .
  
 (3) WHERE THE PIPING SYSTEM IS FOR USE WITH OTHER THAN
 UNDILUTED LIQUEFIED PETROLEUM GASES, DETERMINE THE
 DESIGN SYSTEM PRESSURE, THE ALLOWABLE LOSS IN PRESSURE
 (PRESSURE DROP), AND SPECIFIC GRAVITY OF THE GAS TO BE
 USED IN THE PIPING SYSTEM.
  
 (4) DETERMINE THE LENGTH OF PIPING FROM THE POINT OF
 DELIVERY TO THE MOST REMOTE OUTLET IN THE
 BUILDING/PIPING SYSTEM.
  
  
  
 5. COMPLIED.
 6. COMPLIED.
  
 7. COMPLIED.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  