2014-07-30 11:28:23 | 8100 (8225) IBIS BOULEVARD |
| PERMIT #14050097 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| SHEET GI101 & GI102 - LIFE SAFETY PLANS: INDICATE WHAT |
| MEASURES WILL BE IN PLACE TO ENSURE THE ASSEMBLY AREAS |
| WITHOUT SEATING (SUCH AS BAR TERRACE #214) ARE NOT |
| OVERCROWDED (EXCEED 15 SQ.FT. OCCUPANT LOAD FACTOR). |
| |
| SHEET GI101: THE OCCUPANT LOAD FACTOR FOR KITCHEN |
| SPACES SHALL BE 100 SQ.FT. PER PERSON PER TABLE |
| 7.3.1.2. ALSO KITCHEN #135 ONLY HAS EXIT SIGNAGE |
| LEADING TO ONE EXIT. PROVIDE SIGNAGE FOR SECONDARY |
| MEANS OF EGRESS. |
| |
| SHEET GI101: FORMAL DINING #131 IS APPROXIMATELY 800 |
| SQ.FT. USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER |
| PERSON, THE OCCUPANT LOAD FOR THIS ROOM WOULD BE CLOSER |
| TO 54 PERSONS. ONLY 1 MEANS OF EGRESS IS PROVIDED FOR |
| THIS ROOM. |
| |
| SHEET GI101: FORMAL DINING #130 IS APPROXIMATELY 1600 |
| SQ.FT. USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER |
| PERSON, THE OCCUPANT LOAD FOR THIS ROOM WOULD BE CLOSER |
| TO 107 PERSONS. |
| |
| SHEET GI101: CULTURAL CLASS #125 AND TRAINING #169 |
| APPEAR TO ACTUALLY BE ASSEMBLY USE (15 SQ.FT. OCCUPANT |
| LOAD FACTOR) SPACES AND NOT EDUCATIONAL (20 SQ.FT. |
| OCCUPANT LOAD FACTOR) USE. EDUCATIONAL USE IS DEFINED |
| AS AN OCCUPANCY USED FOR EDUCATIONAL PURPOSES THROUGH |
| THE 12TH GRADE BY SIX OR MORE PERSONS FOR 4 OR MORE |
| HOURS PER DAY OR MORE THAN 12 HOURS PER WEEK. |
| |
| SHEET GI102: THE OCCUPANT LOAD FACTOR FOR KITCHEN |
| SPACES SHALL BE 100 SQ.FT. PER PERSON PER TABLE |
| 7.3.1.2. |
| |
| SHEET GI102: KITCHEN #245 ONLY HAS EXIT SIGNAGE LEADING |
| TO ONE EXIT. PROVIDE SIGNAGE FOR SECONDARY MEANS OF |
| EGRESS. |
| |
| SHEET GI102: GRILL DINING AREA 264A/B IS APPROXIMATELY |
| 3,000 SQ.FT. USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. |
| PER PERSON, THE OCCUPANT LOAD FOR THIS ROOM WOULD BE |
| CLOSER TO 200 PERSONS. |
| |
| SHEET GI102: PROVIDE EXIT SIGNAGE LEADING TO SECONDARY |
| MEANS OF EGRESS FROM LOUNGE #258 AREA. |
| |
| SHEET GI102: PROVIDE A SECONDARY MEANS OF EGRESS AND |
| SIGNAGE FOR BAR TERRACE #214. |
| |
| SHEET AE101: CARD ROOM #185 (71 PERSONS) HAS TWO EXIT |
| ACCESS DOORS THAT HAVE APPROPRIATE SEPARATION; HOWEVER, |
| BOTH DOORS LEAD TO THE SAME CORRIDOR #186 WHEREBY ONE |
| FIRE EVENT COULD COMPROMISE BOTH DOORS. PER SECTION |
| 12.2.5.1.2 THE COMMON PATH OF TRAVEL IS LIMITED TO 75 |
| FEET FOR 50 OR LESS OCCUPANTS AND 20 FEET FOR 51 OR |
| MORE OCCUPANTS. THE EXIT ACCESS DOORS SHALL BE ARRANGED |
| FOR OCCUPANTS TO HAVE ACCESS TO AT LEAST TWO EXITS BY |
| SEPARATE WAYS OF TRAVEL PER SECTION 7.5.1.1.1. |
| |
| SHEET AE101: CULTURAL CLASS #125 (71 PERSONS) HAS TWO |
| EXIT ACCESS DOORS THAT HAVE APPROPRIATE SEPARATION; |
| HOWEVER, BOTH DOORS LEAD TO THE SAME CORRIDOR GALLERY |
| #102 WHEREBY ONE FIRE EVENT COULD COMPROMISE BOTH |
| DOORS. PER SECTION 12.2.5.1.2 THE COMMON PATH OF TRAVEL |
| IS LIMITED TO 75 FEET FOR 50 OR LESS OCCUPANTS AND 20 |
| FEET FOR 51 OR MORE OCCUPANTS. THE EXIT ACCESS DOORS |
| SHALL BE ARRANGED FOR OCCUPANTS TO HAVE ACCESS TO AT |
| LEAST TWO EXITS BY SEPARATE WAYS OF TRAVEL PER SECTION |
| 7.5.1.1.1. |
| |
| SHEET AE101: LOUNGE #110 THE COMMON PATH OF TRAVEL IS |
| 135 FEET. PER SECTION 12.2.5.1.2 THE COMMON PATH OF |
| TRAVEL IS LIMITED TO 75 FEET FOR 50 OR LESS OCCUPANTS |
| AND 20 FEET FOR 51 OR MORE OCCUPANTS. |
| |
| SHEET AE104: MONUMENTAL STAIR #209 APPEARS TO BE |
| FUNCTIONING AS A "COMMUNICATING SPACE" PER NFPA 101 |
| SECTION 8.6.8; HOWEVER, REQUIREMENT #3 REQUIRES THAT |
| SUCH OPENINGS SHALL BE SEPARATED FROM CORRIDORS. |
| |
| SHEET AE105: PROVIDE PANIC HARDWARE FOR UNMARKED |
| SECONDARY EXIT ACCESS DOOR IN BALLROOM #248A. |
| |
| SHEET AE106: BAR TERRACE #214 FEATURES A FIRE PIT. |
| INDICATE IF THE FIRE PIT FLAME WILL BE OPEN OR SCREENED |
| FROM OCCUPANTS. |
| |
| SHEET FP101: RECEIVING #142, MECHANICAL #103 AND |
| STORAGE #126 NOT INDICATED AS ORDINARY HAZARD GROUP 1 |
| PROTECTION. |
| |
| SHEET FP101: WILL THE "COVERED TERRACE" CEILING |
| ADJACENT TO STAIR #4 BE PROTECTED WITH SPRINKLERS? WHAT |
| ABOUT THE OTHER EXTERIOR OVERHAND CEILINGS, SUCH AS BAR |
| TERRACE #214, WILL THEY BE PROTECTED? |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |