2014-07-30 11:28:238100 (8225) IBIS BOULEVARD
 PERMIT #14050097
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET GI101 & GI102 - LIFE SAFETY PLANS: INDICATE WHAT
 MEASURES WILL BE IN PLACE TO ENSURE THE ASSEMBLY AREAS
 WITHOUT SEATING (SUCH AS BAR TERRACE #214) ARE NOT
 OVERCROWDED (EXCEED 15 SQ.FT. OCCUPANT LOAD FACTOR).
  
 SHEET GI101: THE OCCUPANT LOAD FACTOR FOR KITCHEN
 SPACES SHALL BE 100 SQ.FT. PER PERSON PER TABLE
 7.3.1.2. ALSO KITCHEN #135 ONLY HAS EXIT SIGNAGE
 LEADING TO ONE EXIT. PROVIDE SIGNAGE FOR SECONDARY
 MEANS OF EGRESS.
  
 SHEET GI101: FORMAL DINING #131 IS APPROXIMATELY 800
 SQ.FT. USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER
 PERSON, THE OCCUPANT LOAD FOR THIS ROOM WOULD BE CLOSER
 TO 54 PERSONS. ONLY 1 MEANS OF EGRESS IS PROVIDED FOR
 THIS ROOM.
  
 SHEET GI101: FORMAL DINING #130 IS APPROXIMATELY 1600
 SQ.FT. USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER
 PERSON, THE OCCUPANT LOAD FOR THIS ROOM WOULD BE CLOSER
 TO 107 PERSONS.
  
 SHEET GI101: CULTURAL CLASS #125 AND TRAINING #169
 APPEAR TO ACTUALLY BE ASSEMBLY USE (15 SQ.FT. OCCUPANT
 LOAD FACTOR) SPACES AND NOT EDUCATIONAL (20 SQ.FT.
 OCCUPANT LOAD FACTOR) USE. EDUCATIONAL USE IS DEFINED
 AS AN OCCUPANCY USED FOR EDUCATIONAL PURPOSES THROUGH
 THE 12TH GRADE BY SIX OR MORE PERSONS FOR 4 OR MORE
 HOURS PER DAY OR MORE THAN 12 HOURS PER WEEK.
  
 SHEET GI102: THE OCCUPANT LOAD FACTOR FOR KITCHEN
 SPACES SHALL BE 100 SQ.FT. PER PERSON PER TABLE
 7.3.1.2.
  
 SHEET GI102: KITCHEN #245 ONLY HAS EXIT SIGNAGE LEADING
 TO ONE EXIT. PROVIDE SIGNAGE FOR SECONDARY MEANS OF
 EGRESS.
  
 SHEET GI102: GRILL DINING AREA 264A/B IS APPROXIMATELY
 3,000 SQ.FT. USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT.
 PER PERSON, THE OCCUPANT LOAD FOR THIS ROOM WOULD BE
 CLOSER TO 200 PERSONS.
  
 SHEET GI102: PROVIDE EXIT SIGNAGE LEADING TO SECONDARY
 MEANS OF EGRESS FROM LOUNGE #258 AREA.
  
 SHEET GI102: PROVIDE A SECONDARY MEANS OF EGRESS AND
 SIGNAGE FOR BAR TERRACE #214.
  
 SHEET AE101: CARD ROOM #185 (71 PERSONS) HAS TWO EXIT
 ACCESS DOORS THAT HAVE APPROPRIATE SEPARATION; HOWEVER,
 BOTH DOORS LEAD TO THE SAME CORRIDOR #186 WHEREBY ONE
 FIRE EVENT COULD COMPROMISE BOTH DOORS. PER SECTION
 12.2.5.1.2 THE COMMON PATH OF TRAVEL IS LIMITED TO 75
 FEET FOR 50 OR LESS OCCUPANTS AND 20 FEET FOR 51 OR
 MORE OCCUPANTS. THE EXIT ACCESS DOORS SHALL BE ARRANGED
 FOR OCCUPANTS TO HAVE ACCESS TO AT LEAST TWO EXITS BY
 SEPARATE WAYS OF TRAVEL PER SECTION 7.5.1.1.1.
  
 SHEET AE101: CULTURAL CLASS #125 (71 PERSONS) HAS TWO
 EXIT ACCESS DOORS THAT HAVE APPROPRIATE SEPARATION;
 HOWEVER, BOTH DOORS LEAD TO THE SAME CORRIDOR GALLERY
 #102 WHEREBY ONE FIRE EVENT COULD COMPROMISE BOTH
 DOORS. PER SECTION 12.2.5.1.2 THE COMMON PATH OF TRAVEL
 IS LIMITED TO 75 FEET FOR 50 OR LESS OCCUPANTS AND 20
 FEET FOR 51 OR MORE OCCUPANTS. THE EXIT ACCESS DOORS
 SHALL BE ARRANGED FOR OCCUPANTS TO HAVE ACCESS TO AT
 LEAST TWO EXITS BY SEPARATE WAYS OF TRAVEL PER SECTION
 7.5.1.1.1.
  
 SHEET AE101: LOUNGE #110 THE COMMON PATH OF TRAVEL IS
 135 FEET. PER SECTION 12.2.5.1.2 THE COMMON PATH OF
 TRAVEL IS LIMITED TO 75 FEET FOR 50 OR LESS OCCUPANTS
 AND 20 FEET FOR 51 OR MORE OCCUPANTS.
  
 SHEET AE104: MONUMENTAL STAIR #209 APPEARS TO BE
 FUNCTIONING AS A "COMMUNICATING SPACE" PER NFPA 101
 SECTION 8.6.8; HOWEVER, REQUIREMENT #3 REQUIRES THAT
 SUCH OPENINGS SHALL BE SEPARATED FROM CORRIDORS.
  
 SHEET AE105: PROVIDE PANIC HARDWARE FOR UNMARKED
 SECONDARY EXIT ACCESS DOOR IN BALLROOM #248A.
  
 SHEET AE106: BAR TERRACE #214 FEATURES A FIRE PIT.
 INDICATE IF THE FIRE PIT FLAME WILL BE OPEN OR SCREENED
 FROM OCCUPANTS.
  
 SHEET FP101: RECEIVING #142, MECHANICAL #103 AND
 STORAGE #126 NOT INDICATED AS ORDINARY HAZARD GROUP 1
 PROTECTION.
  
 SHEET FP101: WILL THE "COVERED TERRACE" CEILING
 ADJACENT TO STAIR #4 BE PROTECTED WITH SPRINKLERS? WHAT
 ABOUT THE OTHER EXTERIOR OVERHAND CEILINGS, SUCH AS BAR
 TERRACE #214, WILL THEY BE PROTECTED?
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730