2014-08-01 06:45:15 | BUILDING PLAN REVIEW |
| PERMIT: 14050097 |
| ADD: 8100 IBIS BLVD |
| CONT:THE WEITZ CO. |
| TEL: (561)686-5511 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| NOTICE TO DESIGNER OF RECORD. THERE WERE NO CHANGES |
| MADE TO THE PLANS. THERE ARE NO REVISION NUMBERS ON ANY |
| OF THE SHEETS INDICATING WHERE CORRCTIONS WERE MADE TO |
| THE PLANS NOR THROUGH PROJECT DOX DOES VERSION 2 EXIT |
| SHOWING CORRECTIONS WERE MADE. |
| |
| IGNORED!!! A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| NOTICE TO THE DESIGNER OF RECORD!!!! CHAPTER |
| 553.80(2)(B) FLORIDA STATUTES STATES THAT A LOCAL |
| GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE FEE FOR |
| PLAN REVIEW, IF PLANS ARE REJECTED THREE OR MORE TIMES |
| FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION. |
| |
| 2ND REVIEW |
| DATE: FRI. AUG. 01/ 2014 |
| ACTION: DENIED |
| |
| 1) 2ND REQUEST. NOTE SHEET G-1 101 LIFE SAFETY SHEET |
| LOWER LEVEL UNDERTHE HEADING USE & OCCUPANCY INDICATES |
| THE KITCHEN AS 200 GROSS, THE FIRE COMMENT STATES THAT |
| UNDER THE FIRE CODES THEY USE 100 SF/ OCCUPANT. WHEN |
| THERE IS A DIFFERENCE IN CODES, THE MOST RESTRICTIVE |
| SHALL APPLY. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION 102.1. |
| |
| 1A) 2ND REQUEST. THE BUILDING CODE ANALYSIS FOUND ON |
| G-1-101 DOES NOT INDICATE IF THE OCCUPANCIES ARE |
| DESIGNED AS SEPARATED OR NON-SEPARATED? |
| 2010 FBC-B 508.3 OR 508.4. |
| |
| 1B) 2ND REQUEST. G1-101 DINING ROOM 131 INDICATES A |
| OCCUPANCY LOAD OF 67 TRAVELING THROUGH THE EXTERIOR |
| DOUBLE DOORS. WHEN FIGURING THE OCCUPANCY LOAD AT 15 SQ |
| FT / OCC WITHOUT THE BAR THE LOAD IS APPROX. 60 |
| OCCUPANTS WHICH WILL REQUIRE A 2ND EXIT. 2010 FBC-B |
| 1008.1.2. |
| PLEASE ALSO UPDATE THE AMOUNT OF OCCUPANTS THAT WILL BE |
| TRAVELING THROUGH THE EXTERIOR DOUBLE DOORS. |
| |
| 1C) 2ND REQUEST. G1-101 CARD ROOM 185 HAS (2) EXIT |
| DOORS THAT CONVERGE INTO A SINGLE MEANS OF EGRESS, |
| THERE IS NO 2 SEPARATE MEANS OF EGRESS FROM THIS ROOM. |
| A CONVERGING MENAS OF EGRESS. |
| |
| 1D) 2ND REQUEST. IN BOTH THE CULTURAL CLASS # 125 & THE |
| TRAINING ROOM # 169 ARE BOTH TAKEN AT 20 SQ FT/ OCC. |
| THE 20 SQ FT IS TAKEN WITH AN EDUCATIONAL SETTING |
| KINDERGADEN -12TH GRADE. FOR ADULT EDUCATION IN |
| COLLEGES IT IS CONSIDERED BUSINESS OCCUPANCY. THIS IS A |
| MULTI-PURPOSE ROOM WHERE A NASSEMBLY OCCUPANCY CAN BE |
| TAKEN AT 15 SQ FT/ OCCUPANT. 2010 FBC-B TABLE 1004.1.1. |
| |
| 2) SHEET AE105: |
| |
| 2A) 2ND REQUEST. MEETING ROOMS 225 A& B BOTH INDICATE |
| THE USE OF A NANAWALL SYSTEM, PLEASE PROVIDE THE |
| MANUFACTURERS SPECIFICATION AS TO HOW THIS SYSTEM WILL |
| FOLD BACK AND NOT PROJECT INTO THE EXIT ACCESS CORRIDOR |
| MORETHAN (7INCHES). 2010 FBC-B 1008.1.9.11 |
| DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL |
| LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED |
| WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING, |
| NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE |
| REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR |
| LANDING, WHEN FULLY OPEN. |
| |
| 2B) 2ND REQUEST. THE MONUMENTAL STAIR # 209 INDICATES |
| SEE DETAIL #5/ AE.402 THIS DETAIL DIRECTS YOU TO DETAIL |
| # 1/ A320 THIS IS A ELEVATION CUT SECTION THROUGH THE |
| MONUMENTAL STAIR. PLEASE SEE 2010 FBC-B SECTION 708.2 |
| EXCEPTION 2.1 THAT REQUIRES A DRAFT CURTAIN AND CLOSELY |
| SPACED SPRINKLERS IN ACCORDANCE WITH NFPA 13. |
| |
| 3) 2ND REQUEST. AE401 PLEASE REVIEW THE 2010 |
| FBC-ACCESSIBILITY CODE SECTION 213.3.1 TOILET |
| COMPARTMENTS. |
| WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE |
| TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN |
| ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH |
| 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH |
| 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE |
| PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER |
| CLOSETS TOTALS SIX OR MORE FIXTURES. |
| 604.8.2 AMBULATORY ACCESSIBLE COMPARTMENTS. |
| 604.8.2.1 SIZE. |
| AMBULATORY ACCESSIBLE COMPARTMENTS SHALL HAVE A DEPTH |
| OF 60 INCHES (1525 MM) MINIMUM AND A WIDTH OF 35 INCHES |
| (890 MM) MINIMUM AND 37 INCHES (940 MM) MAXIMUM. |
| |
| 604.8.2.2 DOORS. |
| TOILET COMPARTMENT DOORS, INCLUDING DOOR HARDWARE, |
| SHALL COMPLY WITH 404, EXCEPT THAT IF THE APPROACH IS |
| TO THE LATCH SIDE OF THE COMPARTMENT DOOR, CLEARANCE |
| BETWEEN THE DOOR SIDE OF THE COMPARTMENT AND ANY |
| OBSTRUCTION SHALL BE 42 INCHES (1065 MM) MINIMUM. |
| |
| THE DOOR SHALL BE SELF-CLOSING. A DOOR PULL COMPLYING |
| WITH 404.2.7 SHALL BE PLACED ON BOTH SIDES OF THE DOOR |
| NEAR THE LATCH. TOILET |
| COMPARTMENT DOORS SHALL NOT SWING INTO THE MINIMUM |
| REQUIRED COMPARTMENT AREA. |
| |
| 4) 2ND REQUEST. SHEET AE501: |
| 4A) DRINKING FOUNTAINS MUST COMPLY WITH 2 HEIGHTS: 2010 |
| FL ACC CODE 211.2 MINIMUM NUMBER. |
| NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| 602.7. |
| |
| 4B) 2ND REQUEST. THE GRAB BAR RANGE IS THE SAME BUT THE |
| HEIGHT OF THE GRAB BAR IS NO LONGER TO THE CENTERLINE |
| OF THE GRAB BAR BUT TO TOP OF THE GRIPPING SURFACE SEE |
| 2010 FL ACC CODE 609.4. |
| |
| 5) COMPLIED, SPOKE WITH ENGINEER, SHOWED ME WHICH SHEET |
| THEY WERE LOCATED. |
| |
| |
| 6) 2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| 7) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 8) 2ND REQUEST. THE PLANS INDICATE THIS IS A TYPE IIIA |
| BUILDING, PLEASE PROVIDE HOW COMPLIANCE WITH 2010 FBC-B |
| TABLE 601 FIRE RATINGS WILL BE ACHIEVED. |
| |
| 9) 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |