Plan Review Notes
Plan Review Notes For Permit 14050097
Permit Number 14050097
Review Stop B
Sequence Number 2
Notes
Date Text
2014-08-01 06:45:15BUILDING PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 NOTICE TO DESIGNER OF RECORD. THERE WERE NO CHANGES
 MADE TO THE PLANS. THERE ARE NO REVISION NUMBERS ON ANY
 OF THE SHEETS INDICATING WHERE CORRCTIONS WERE MADE TO
 THE PLANS NOR THROUGH PROJECT DOX DOES VERSION 2 EXIT
 SHOWING CORRECTIONS WERE MADE.
  
 IGNORED!!! A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 NOTICE TO THE DESIGNER OF RECORD!!!! CHAPTER
 553.80(2)(B) FLORIDA STATUTES STATES THAT A LOCAL
 GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE OR MORE TIMES
 FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
 2ND REVIEW
 DATE: FRI. AUG. 01/ 2014
 ACTION: DENIED
  
 1) 2ND REQUEST. NOTE SHEET G-1 101 LIFE SAFETY SHEET
 LOWER LEVEL UNDERTHE HEADING USE & OCCUPANCY INDICATES
 THE KITCHEN AS 200 GROSS, THE FIRE COMMENT STATES THAT
 UNDER THE FIRE CODES THEY USE 100 SF/ OCCUPANT. WHEN
 THERE IS A DIFFERENCE IN CODES, THE MOST RESTRICTIVE
 SHALL APPLY. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION 102.1.
  
 1A) 2ND REQUEST. THE BUILDING CODE ANALYSIS FOUND ON
 G-1-101 DOES NOT INDICATE IF THE OCCUPANCIES ARE
 DESIGNED AS SEPARATED OR NON-SEPARATED?
 2010 FBC-B 508.3 OR 508.4.
  
 1B) 2ND REQUEST. G1-101 DINING ROOM 131 INDICATES A
 OCCUPANCY LOAD OF 67 TRAVELING THROUGH THE EXTERIOR
 DOUBLE DOORS. WHEN FIGURING THE OCCUPANCY LOAD AT 15 SQ
 FT / OCC WITHOUT THE BAR THE LOAD IS APPROX. 60
 OCCUPANTS WHICH WILL REQUIRE A 2ND EXIT. 2010 FBC-B
 1008.1.2.
 PLEASE ALSO UPDATE THE AMOUNT OF OCCUPANTS THAT WILL BE
 TRAVELING THROUGH THE EXTERIOR DOUBLE DOORS.
  
 1C) 2ND REQUEST. G1-101 CARD ROOM 185 HAS (2) EXIT
 DOORS THAT CONVERGE INTO A SINGLE MEANS OF EGRESS,
 THERE IS NO 2 SEPARATE MEANS OF EGRESS FROM THIS ROOM.
 A CONVERGING MENAS OF EGRESS.
  
 1D) 2ND REQUEST. IN BOTH THE CULTURAL CLASS # 125 & THE
 TRAINING ROOM # 169 ARE BOTH TAKEN AT 20 SQ FT/ OCC.
 THE 20 SQ FT IS TAKEN WITH AN EDUCATIONAL SETTING
 KINDERGADEN -12TH GRADE. FOR ADULT EDUCATION IN
 COLLEGES IT IS CONSIDERED BUSINESS OCCUPANCY. THIS IS A
 MULTI-PURPOSE ROOM WHERE A NASSEMBLY OCCUPANCY CAN BE
 TAKEN AT 15 SQ FT/ OCCUPANT. 2010 FBC-B TABLE 1004.1.1.
  
 2) SHEET AE105:
  
 2A) 2ND REQUEST. MEETING ROOMS 225 A& B BOTH INDICATE
 THE USE OF A NANAWALL SYSTEM, PLEASE PROVIDE THE
 MANUFACTURERS SPECIFICATION AS TO HOW THIS SYSTEM WILL
 FOLD BACK AND NOT PROJECT INTO THE EXIT ACCESS CORRIDOR
 MORETHAN (7INCHES). 2010 FBC-B 1008.1.9.11
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR
 LANDING, WHEN FULLY OPEN.
  
 2B) 2ND REQUEST. THE MONUMENTAL STAIR # 209 INDICATES
 SEE DETAIL #5/ AE.402 THIS DETAIL DIRECTS YOU TO DETAIL
 # 1/ A320 THIS IS A ELEVATION CUT SECTION THROUGH THE
 MONUMENTAL STAIR. PLEASE SEE 2010 FBC-B SECTION 708.2
 EXCEPTION 2.1 THAT REQUIRES A DRAFT CURTAIN AND CLOSELY
 SPACED SPRINKLERS IN ACCORDANCE WITH NFPA 13.
  
 3) 2ND REQUEST. AE401 PLEASE REVIEW THE 2010
 FBC-ACCESSIBILITY CODE SECTION 213.3.1 TOILET
 COMPARTMENTS.
 WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE
 TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN
 ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH
 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH
 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE
 PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER
 CLOSETS TOTALS SIX OR MORE FIXTURES.
 604.8.2 AMBULATORY ACCESSIBLE COMPARTMENTS.
 604.8.2.1 SIZE.
 AMBULATORY ACCESSIBLE COMPARTMENTS SHALL HAVE A DEPTH
 OF 60 INCHES (1525 MM) MINIMUM AND A WIDTH OF 35 INCHES
 (890 MM) MINIMUM AND 37 INCHES (940 MM) MAXIMUM.
  
 604.8.2.2 DOORS.
 TOILET COMPARTMENT DOORS, INCLUDING DOOR HARDWARE,
 SHALL COMPLY WITH 404, EXCEPT THAT IF THE APPROACH IS
 TO THE LATCH SIDE OF THE COMPARTMENT DOOR, CLEARANCE
 BETWEEN THE DOOR SIDE OF THE COMPARTMENT AND ANY
 OBSTRUCTION SHALL BE 42 INCHES (1065 MM) MINIMUM.
  
 THE DOOR SHALL BE SELF-CLOSING. A DOOR PULL COMPLYING
 WITH 404.2.7 SHALL BE PLACED ON BOTH SIDES OF THE DOOR
 NEAR THE LATCH. TOILET
 COMPARTMENT DOORS SHALL NOT SWING INTO THE MINIMUM
 REQUIRED COMPARTMENT AREA.
  
 4) 2ND REQUEST. SHEET AE501:
 4A) DRINKING FOUNTAINS MUST COMPLY WITH 2 HEIGHTS: 2010
 FL ACC CODE 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 4B) 2ND REQUEST. THE GRAB BAR RANGE IS THE SAME BUT THE
 HEIGHT OF THE GRAB BAR IS NO LONGER TO THE CENTERLINE
 OF THE GRAB BAR BUT TO TOP OF THE GRIPPING SURFACE SEE
 2010 FL ACC CODE 609.4.
  
 5) COMPLIED, SPOKE WITH ENGINEER, SHOWED ME WHICH SHEET
 THEY WERE LOCATED.
  
  
 6) 2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 7) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) 2ND REQUEST. THE PLANS INDICATE THIS IS A TYPE IIIA
 BUILDING, PLEASE PROVIDE HOW COMPLIANCE WITH 2010 FBC-B
 TABLE 601 FIRE RATINGS WILL BE ACHIEVED.
  
 9) 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  