2014-07-05 12:43:58BUILDING PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JULY 12/ 2014
 ACTION: DENIED
  
 1) SHEET P105 NOR 305 DOES NOT INDICATE THE SIZE OF THE
 VERTICAL CONDUCTORS AND LEADERS, BUILDING STORM DRAINS,
 BUILDING STORM SEWERS, AND ANY HORIZONTAL BRANCHES OF
 SUCH DRAINS OR SEWERS SHALL BE BASED ON THE 100-YEAR
 HOURLY RAINFALL RATE INDICATED IN FIGURE 1106.1 OR ON
 OTHER RAINFALL RATES DETERMINED FROM APPROVED LOCAL
 WEATHER DATA. 2010 FBC-P 1106.1.
  
 2) P105 DOES NOT PROVIDE WHAT AREA THE ROOF DRAINS ARE
 RECEIVING, IF THIS IS JUST THE FLAT AREA OR IF THIS
 AREA IS ALSO THE CONTRIBUTING SLOPED ARAES, PLEASE
 PROVIDE A BREAK OUT FOR EACH ROOF DRAIN SERVED OF FLAT
 AND ADJOINING SLOPED ROOFS THAT CONTRIBUTE TO THE ROOF
 DRAIN LOAD.
 2010 1106.4.
  
 3) SHEET P201 VERSES P301
 3A) THE LADIES RESTROOM 222 THE 4 WATER CLOSETS IN A
 ROW IS MISSING THE VENT CONNECTION FOR A CIRCUIT VENT
 SEE SECTION 2010 FBC-P 911.2.
  
 3B) IT APPEARS ONE OF THE WATER CLOSETS IN THE MENS
 RESTROOM IS NOT VENTEDAS A INDIVDUAL VENT OF THE
 BEGINNING OF A CIRCUIT VENT SEE 2010 FBC-P 907.1 &
 911.2. T
  
 3C) IT APPEARS ONE OF THE WATER CLOSETS IN THE MENS
 RESTROOM IS NOT VENTEDAS A INDIVDUAL VENT OF THE
 BEGINNING OF A CIRCUIT VENT SEE 2010 FBC-P 907.1 &
 911.2. T
  
 4A) 0173-P304 RISER E GREASE WASTE, THE PLANS INDICATE
 THE GREASE WASTE FROM KITCHENS # 135 & #245, THE PLANS
 DO NOT COMMENT ON THE DRAINAGE FIXTURE UNITS FOR THE
 GREASE WASTE NOR MENTION SIZING NOR THE LOCATION OF THE
 GREASE INTERCEPTOR. 2010 FBC-PLUMBING 1003.2. APPROVAL.
 1003.3.3 SIZED. NOTE IF A CONCRETE VAULT TYPE OF
 INTERCEPTOR IS TO BE INSTALLED PLEASE NOTE THAT FBC-P
 TABLE 1003.5.1 IS THE SIZING TABLE TO BE USED FOR THIS
 TYPE OF APPLICATION.
  
 4B) THE PLANS DO NOT INDICATE IF ANY FOOD WASSTE
 GRINDERS ARE GOING TO BE INSTALLED. 2010 FBC-PLUMBING
 1003.3.2.
  
 4C) THE ARCHITECTURAL SHEETS & STRURTURAL SHEETS BOTH
 INDICATE THE ELEVATOR PIT TO HAVE A SUMP PIT. PLANS ARE
 NOT CLEAR IF THIS IS TO BE A HYDROLIC ELEVATOR, IF SO
 PLEASE INDICATE HOW COMPLIANCE WITH 2010 FBC-PLUMBING
 1003.4 OIL SPEARATOR REQUIRED WILL BE ACHIEVED. I DID
 NOT SEE A DETAIL FOR A SUMP IN THE ELEVATOR PIT AND
 WASTE CONNECTIONS.SHEET P401 DOES INDICATE THE USE OF
 ZOELLER SUBMERSIBLE SUMP PUMP EXCEPTION: AN OIL
 SEPARATOR IS NOT REQUIRED IN HYDRAULIC ELEVATOR PITS
 WHERE AN APPROVED ALARM SYSTEM IS INSTALLED.
  
 1003.4.2 OIL SEPARATOR DESIGN.
 OIL SEPARATORS SHALL BE DESIGNED IN ACCORDANCE WITH
 SECTIONS 1003.4.2.1 AND 1003.4.2.2.
  
 1003.4.2.1 GENERAL DESIGN REQUIREMENTS.
 OIL SEPARATORS SHALL HAVE A DEPTH OF NOT LESS THAN 2
 FEET (610 MM) BELOW THE INVERT OF THE DISCHARGE DRAIN.
 THE OUTLET OPENING OF THE SEPARATOR SHALL HAVE NOT LESS
 THAN AN 18-INCH (457 MM) WATER SEAL.
  
 5) SHEET 0176- P401 PLUMBING SCHEDULE. TTRAP PRIMERS
 INDICATE PRECISION PLUMBING PRODUCTS BUT THE ACTUAL
 TYPE OR MODEL NUMBER IS NOT INDICATED NOR IS THE
 CONFORMANCE FOR TRAP SEAL PRIMER VALVES TO COMPLY WITH
 ASSE 1018 OR ASSE 1044. 2010 FBC-P 1002.4.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved