Plan Review Notes For Permit 14050097 |
Permit Number |
14050097 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-07-17 10:03:51 | PASS PROVISO | | 1) PROVIDE A DETAIL FROM THE ENGINEER FOR THE | | EXHAUST FANS AND SUPPLY FANS CURBS TIE DOWN TO ROOF | | AND FANS TIE DOWN TO CURB . PER SECTION 301.12 | | WIND RESISTANCE 2010 FBC (M) | | 2) INSPECTOR WILL CHECK THE 16GA X 2IN G-90 GALV. | | STEEL EXTERIOR STRAP WHEN INSPECTING CURB TIE DOWN TO | | ROOF | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|