Plan Review Notes
Plan Review Notes For Permit 14050097
Permit Number 14050097
Review Stop B
Sequence Number 1
Notes
Date Text
2014-07-05 12:43:32BUILDING PLAN REVIEW
 PERMIT: 14050097
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JULY 12/ 2014
 ACTION: DENIED
  
 1) NOTE SHEET G-1 101 LIFE SAFETY SHEET LOWER LEVEL
 UNDERTHE HEADING USE & OCCUPANCY INDICATES THE KITCHEN
 AS 200 GROSS, THE FIRE COMMENT STATES THAT UNDER THE
 FIRE CODES THEY USE 100 SF/ OCCUPANT. WHEN THERE IS A
 DIFFERENCE IN CODES, THE MOST RESTRICTIVE SHALL APPLY.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 102.1.
  
 1A) THE BUILDING CODE ANALYSIS FOUND ON G-1-101 DOES
 NOT INDICATE IF THE OCCUPANCIES ARE DESIGNED AS
 SEPARATED OR NON-SEPARATED?
 2010 FBC-B 508.3 OR 508.4.
  
 1B) G1-101 DINING ROOM 131 INDICATES A OCCUPANCY LOAD
 OF 67 TRAVELING THROUGH THE EXTERIOR DOUBLE DOORS. WHEN
 FIGURING THE OCCUPANCY LOAD AT 15 SQ FT / OCC WITHOUT
 THE BAR THE LOAD IS APPROX. 60 OCCUPANTS WHICH WILL
 REQUIRE A 2ND EXIT. 2010 FBC-B 1008.1.2.
 PLEASE ALSO UPDATE THE AMOUNT OF OCCUPANTS THAT WILL BE
 TRAVELING THROUGH THE EXTERIOR DOUBLE DOORS.
  
 1C) G1-101 CARD ROOM 185 HAS (2) EXIT DOORS THAT
 CONVERGE INTO A SINGLE MEANS OF EGRESS, THERE IS NO 2
 SEPARATE MEANS OF EGRESS FROM THIS ROOM. A CONVERGING
 MENAS OF EGRESS.
  
 1D) IN BOTH THE CULTURAL CLASS # 125 & THE TRAINING
 ROOM # 169 ARE BOTH TAKEN AT 20 SQ FT/ OCC. THE 20 SQ
 FT IS TAKEN WITH AN EDUCATIONAL SETTING KINDERGADEN
 -12TH GRADE. FOR ADULT EDUCATION IN COLLEGES IT IS
 CONSIDERED BUSINESS OCCUPANCY. THIS IS A MULTI-PURPOSE
 ROOM WHERE A NASSEMBLY OCCUPANCY CAN BE TAKEN AT 15 SQ
 FT/ OCCUPANT. 2010 FBC-B TABLE 1004.1.1.
  
 2) SHEET AE105:
  
 2A) MEETING ROOMS 225 A& B BOTH INDICATE THE USE OF A
 NANAWALL SYSTEM, PLEASE PROVIDE THE MANUFACTURERS
 SPECIFICATION AS TO HOW THIS SYSTEM WILL FOLD BACK AND
 NOT PROJECT INTO THE EXIT ACCESS CORRIDOR MORETHAN
 (7INCHES). 2010 FBC-B 1008.1.9.11
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR
 LANDING, WHEN FULLY OPEN.
  
 2B) THE MONUMENTAL STAIR # 209 INDICATES SEE DETAIL #5/
 AE.402 THIS DETAIL DIRECTS YOU TO DETAIL # 1/ A320 THIS
 IS A ELEVATION CUT SECTION THROUGH THE MONUMENTAL
 STAIR. PLEASE SEE 2010 FBC-B SECTION 708.2 EXCEPTION
 2.1 THAT REQUIRES A DRAFT CURTAIN AND CLOSELY SPACED
 SPRINKLERS IN ACCORDANCE WITH NFPA 13.
  
 3) AE401 PLEASE REVIEW THE 2010 FBC-ACCESSIBILITY CODE
 SECTION 213.3.1 TOILET COMPARTMENTS.
 WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE
 TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN
 ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH
 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH
 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE
 PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER
 CLOSETS TOTALS SIX OR MORE FIXTURES.
 604.8.2 AMBULATORY ACCESSIBLE COMPARTMENTS.
 604.8.2.1 SIZE.
 AMBULATORY ACCESSIBLE COMPARTMENTS SHALL HAVE A DEPTH
 OF 60 INCHES (1525 MM) MINIMUM AND A WIDTH OF 35 INCHES
 (890 MM) MINIMUM AND 37 INCHES (940 MM) MAXIMUM.
  
 604.8.2.2 DOORS.
 TOILET COMPARTMENT DOORS, INCLUDING DOOR HARDWARE,
 SHALL COMPLY WITH 404, EXCEPT THAT IF THE APPROACH IS
 TO THE LATCH SIDE OF THE COMPARTMENT DOOR, CLEARANCE
 BETWEEN THE DOOR SIDE OF THE COMPARTMENT AND ANY
 OBSTRUCTION SHALL BE 42 INCHES (1065 MM) MINIMUM.
  
 THE DOOR SHALL BE SELF-CLOSING. A DOOR PULL COMPLYING
 WITH 404.2.7 SHALL BE PLACED ON BOTH SIDES OF THE DOOR
 NEAR THE LATCH. TOILET
 COMPARTMENT DOORS SHALL NOT SWING INTO THE MINIMUM
 REQUIRED COMPARTMENT AREA.
  
 4) SHEET AE501:
 4A) DRINKING FOUNTAINS MUST COMPLY WITH 2 HEIGHTS: 2010
 FL ACC CODE 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 4B) THE GRAB BAR RANGE IS THE SAME BUT THE HEIGHT OF
 THE GRAB BAR IS NO LONGER TO THE CENTERLINE OF THE GRAB
 BAR BUT TO TOP OF THE GRIPPING SURFACE SEE 2010 FL ACC
 CODE 609.4.
  
 5) THE STRUCTURAL SHEETS PROVIDE THE PRESSURES FOR THE
 ROOF IN VULT & VASD BUT THERE ARE NO PRESSURES GIVEN
 FOR THE WALL OPENINGS INTERIOR WALL ZONE 4 NOR THE
 CORNER WALL ZONE # 5. 2010 FBC-B 1609.6 .2010 FBC-B
 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF
 ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
  
  
 6) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) THE PLANS INDICATE THIS IS A TYPE IIIA BUILDING,
 PLEASE PROVIDE HOW COMPLIANCE WITH 2010 FBC-B TABLE 601
 FIRE RATINGS WILL BE ACHIEVED.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  