Plan Review Notes
Plan Review Notes For Permit 14050002
Permit Number 14050002
Review Stop B
Sequence Number 1
Notes
Date Text
2014-05-09 10:58:44THE REISSUANCE APPLICATION HAS BEEN SUBMITTED WITH A
 CONTRACTOR IDENTIFIED AS EXEMPT FROM FS 489 LICENSING
 REQUIREMENTS. THE REMAINING SCOPE OF WORK FOR THE
 COMPLETION OF THIS PERMIT MAY NOT QUALIFY FOR THE
 EXEMPTION. PLEASE IDENTIFY EXACTLY WHICH EXEMPTION
 LISTED IN FS 489.103 IS APPLICABLE TO THIS APPLICATION.
 THE RECORD INDICATES SOME WORK WAS COMPLETED IN THE
 PAST, BUT ALONG WITH REVIEW OF THE ORIGINAL PLAN, A
 PLAN WITH REVISED DATE OF 10/17/13 HAS BEEN SUBMITTED.
 THE NEWER PLANS INDICATE ELECTRICAL AND PLUMBING WORK
 INCONSISTENT WITH THE ORIGINAL PLAN AS TO LOCATION. THE
 ORIGINAL ELECTRICAL AND PLUMBING SUB PERMITS WERE
 FINALED WITH THE ORIGINAL PLAN. HAS THE SINK LOCATION
 AND ELECTRICAL BEEN MOVED SINCE THE FINAL ELECTRICAL
 AND PLUMBING INSPECTIONS WERE PERFORMED? IF SO, NEW
 ELECTRICAL AND PLUMBING SUB PERMITS ARE REQUIRED, THE
 MACHANICAL SCOPE OF WORK HAS ALSO BEEN CHANGED IN THE
 REVISED PLAN. A REVISION SUBMITTAL OF THE
 AFOREMENTIONED CHANGES IS REQUIRED. SEE FBC 107.4
 BELOW. ADDITIONAL FEES WILL APPLY. THE REVISED DRAWINGS
 SHOULD BE SUBMITTED AFTER THE PERMIT IS REISSUED.
 ALTERNATIVELY, A REVISION APPLICATION MAY BE SUBMITTED
 AT THIS TIME HOWEVER, ONE ADDITIONAL SET OF THE REVISED
 PLAN IS REQUIRED.
  
 FBC 107.4 AMENDED CONSTRUCTION DOCUMENTS. WORK SHALL BE
 INSTALLED IN ACCORDANCE WITH THE REVIEWED
 CONSTRUCTION DOCUMENTS, AND ANY CHANGES MADE DURING
 CONSTRUCTION THAT ARE NOT IN COMPLIANCE WITH
 THE REVIEWED CONSTRUCTION DOCUMENTS SHALL BE
 RESUBMITTED FOR REVIEW AS AN AMENDED SET OF
 CONSTRUCTION DOCUMENTS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  
  