Date |
Text |
2014-05-09 10:58:44 | THE REISSUANCE APPLICATION HAS BEEN SUBMITTED WITH A |
| CONTRACTOR IDENTIFIED AS EXEMPT FROM FS 489 LICENSING |
| REQUIREMENTS. THE REMAINING SCOPE OF WORK FOR THE |
| COMPLETION OF THIS PERMIT MAY NOT QUALIFY FOR THE |
| EXEMPTION. PLEASE IDENTIFY EXACTLY WHICH EXEMPTION |
| LISTED IN FS 489.103 IS APPLICABLE TO THIS APPLICATION. |
| THE RECORD INDICATES SOME WORK WAS COMPLETED IN THE |
| PAST, BUT ALONG WITH REVIEW OF THE ORIGINAL PLAN, A |
| PLAN WITH REVISED DATE OF 10/17/13 HAS BEEN SUBMITTED. |
| THE NEWER PLANS INDICATE ELECTRICAL AND PLUMBING WORK |
| INCONSISTENT WITH THE ORIGINAL PLAN AS TO LOCATION. THE |
| ORIGINAL ELECTRICAL AND PLUMBING SUB PERMITS WERE |
| FINALED WITH THE ORIGINAL PLAN. HAS THE SINK LOCATION |
| AND ELECTRICAL BEEN MOVED SINCE THE FINAL ELECTRICAL |
| AND PLUMBING INSPECTIONS WERE PERFORMED? IF SO, NEW |
| ELECTRICAL AND PLUMBING SUB PERMITS ARE REQUIRED, THE |
| MACHANICAL SCOPE OF WORK HAS ALSO BEEN CHANGED IN THE |
| REVISED PLAN. A REVISION SUBMITTAL OF THE |
| AFOREMENTIONED CHANGES IS REQUIRED. SEE FBC 107.4 |
| BELOW. ADDITIONAL FEES WILL APPLY. THE REVISED DRAWINGS |
| SHOULD BE SUBMITTED AFTER THE PERMIT IS REISSUED. |
| ALTERNATIVELY, A REVISION APPLICATION MAY BE SUBMITTED |
| AT THIS TIME HOWEVER, ONE ADDITIONAL SET OF THE REVISED |
| PLAN IS REQUIRED. |
| |
| FBC 107.4 AMENDED CONSTRUCTION DOCUMENTS. WORK SHALL BE |
| INSTALLED IN ACCORDANCE WITH THE REVIEWED |
| CONSTRUCTION DOCUMENTS, AND ANY CHANGES MADE DURING |
| CONSTRUCTION THAT ARE NOT IN COMPLIANCE WITH |
| THE REVIEWED CONSTRUCTION DOCUMENTS SHALL BE |
| RESUBMITTED FOR REVIEW AS AN AMENDED SET OF |
| CONSTRUCTION DOCUMENTS. |
| |
| STEVEN KENNEDY, CBO |
| CHIEF PLANS EXAMINER |
| (561) 805-6710 |