Plan Review Notes
Plan Review Notes For Permit 14041087
Permit Number 14041087
Review Stop E
Sequence Number 1
Notes
Date Text
2014-05-20 14:09:18ELECTRICAL DEFICIENCIES FOR PERMIT 14041087
  
 1. MINIMUM OUTLET PLACEMENT TO COMPLY WITH NEC 210.52
 IS AS MARKED ON SUBMITTED PLANS
 2. AS PER NEC 210.8, ALL KITCHEN OUTLETS SHALL BE GFCI
 PROTECTED.
 3. ALL NEW OUTLET BOXES SHALL COMPLY WITH MINIMUM DEPTH
 REQUIREMENTS OF NEC 314.21.
 4. ALL NEW OUTLETS SHALL COMPLY W/NEC 406.11,
 TAMPER-RESISTANT.
 5. ALL NEW CIRCUITS SHALL COMPLY W/NEC 210.12,
 ARC-FAULT.
 6. PROVIDE A PANEL SCHEDULE
 7. SUBMIT AN ELECTRICAL RISER DIAGRAM W/LOAD CALCS.
 8. IF SERVICE IS BEING UPGRADED, PROVIDE A SITE PLAN
 INDICATING WHERE THE METER AND MAIN DISCONNECT ARE.
  