2014-05-22 15:56:24 | BUILDING PLAN REVIEW |
| PERMIT: 14041084 |
| ADD: 4335 N HAVERHILL RD |
| CONT:LENNAR HOMES, LLC |
| TEL: (954)533-5299X1 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. MAY 22/ 2014 |
| ACTION: DENIED |
| |
| 1) STATE APPROVED PLANS INDICATE SITE INSTALLED ITEMS: |
| 1A) STORM SHUTTERS |
| 1B) ACCESSIBLE STAIRS AND RAMPS |
| |
| 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(E) SHUTTERS |
| |
| 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 4) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC |
| 1609.1.4. |
| FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4, 1714.5.1 & |
| EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A COMPLETE |
| INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING |
| SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT |
| SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS, |
| WALL PRESSURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION TO FACILITATE |
| PLAN REVIEW AND PERMIT ISSUANCE. |
| |
| 5) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| STAIRS CONSTRUCTION/GEOMETRY/ HANDRAILS/ GAURDRAILS |
| 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| FOLLOWING: RAMPS/ HANDRAILS & GAURDRAILS. |
| SITE REQUIREMENTS, ACCESSIBLE ROUTE & VERTICAL |
| ACCESSIBILITY |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |