2014-05-28 14:58:43RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED:
 CALCULATIONS ARE INCOMPLETE. CALCULATIONS NEED TO SHOW
 THE EQUIPMENT MANUFACTURER AND MODEL NUMBER AS REQUIRED
 BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- PLANS AND EQUIPMENT SIZING CALCULATIONS SUBMITTED
 SHOW 2 EXISTING 2.5 TON UNITS. ACCORDING TO CITY
 RECORDS THERE ARE NO PERMITS FOR THE A/C EQUIPMENT
 REPLACEMENT IN THE LAST 14 YEARS. PROVIDE PROOF THAT
 EQUIPMENT IS THE ORIGINAL EQUIPMENT OF THE HOUSE OR
 PROVIDE COMPLETE INFORMATION AS REQUIRED BY SEC.
 101.4.7.1.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 3- A/C PLAN:
 A) PROVIDE NAME AND SIGNATURE OF PERSON RESPONSIBLE FOR
 THE DESIGN. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 B) PROVIDE AL THE EQUIPMENT INFORMATION (MANUFACTURER,
 MODEL ETC). . AND LOCATION INCLUDING THE CONDENSER
 UNIT. SEC. 107.3.5.3(1) CITY AMENDMENTS
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  