Plan Review Notes
Plan Review Notes For Permit 14041064
Permit Number 14041064
Review Stop E
Sequence Number 1
Notes
Date Text
2014-04-30 17:11:55PLEASE PROVIDE HP RATINGS OF ALL MOTORS. NEW AND OR
 EXISTING.
 PLEASE SHOW COMPLIANCE WITH THE NEC 430.32. MOTOR
 OVERLOAD DEVICE TO BE PROVIDED FOR MOTORS OVER ONE HP.
 A SEPARATE FIRE ALARM PERMIT IS REQUIRED.
 THE PLANS INDICATE NEW FIRE ALARM DEVICES. PLEASE
 PROVIDE COMPLETE F/A DRAWINGS TO INCLUDE A LOCATION OF
 THE FACP, BATTERY CALCULATIONS. AND SUBMITTALS ON
 EQUIPMENT.
 THE PLANS INDICATE A EXISTING STANDBY GENERATOR. PLEASE
 PROVIDE ADDITIONAL DETAIL ON THE GENERATOR SPECIFICALLY
 HOW IT TIES INTO THE FACILITY'S ELECTRICAL SYSTEM.
  
  