Plan Review Notes For Permit 14040969 |
Permit Number |
14040969 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-04-29 17:55:57 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. EGRESS IS SHOWN AS A SCREEN INSTALLED OVER AN | | OUTSWING DOOR. PROVIDE A DETAIL TO SHOW HOW THE DOOR | | WILL OPERATE WITH THE SHUTTER INSTALLED. INSTALLATION | | SCHEDULE INDICATES THAT THE SHUTTER GLASS SEPARATION IS | | 0. SEE FBC 2010 RESIDENTIAL 310.4. | | | | 2. SPANS NOT CLEAR. FOR INSTANCE, SEE OPENING 1. A | | 40X66 (WXH), VERTICAL INSTALLATION, 4" EDGE DISTANCE, | | SHOULD HAVE A SPAN BETWEEN 66" AND 74", DEPENDING ON | | INSTALLATION METHOD, BUT SPAN IS 40" ON THE | | INSTALLATION SCHEDULE. SHUTTER MOUNTING CONNECTION TYPE | | IS NOTED AS "TYPICAL", BUT "TYPICAL" IN THE PRODUCT | | APPROVAL INCLUDES MANY DIFFERENT OPTIONS. REVISE SPANS | | AND PROVIDE MORE SPECIFIC INFORMATION IF NECESSARY. | | | | 3. FASTENER PROPOSED NOT CLEAR. SEE PAGE 2; FOUR | | DIFFERENT TYPES OF LAGS WITH DIFFERENT LIMITATIONS. | | REVISE FASTENER TO BE SPECIFIC AS TO WHICH OF THE FOUR | | LAGS IS PROPOSED. | | | | 4. EDGE DISTANCE IS 4", FOR WOOD, NOT CLEAR IF THIS IS | | POSSIBLE. THIS WOULD REQUIRE 8" OF STRUCTURAL WOOD | | SUBSTRATE, TOP AND BOTTOM, BUT THIS IS NOT TYPICAL OF | | WOOD FRAME STRUCTURES. PLEASE CLARIFY OR REVISE. | | | | | | |
|