Plan Review Notes
Plan Review Notes For Permit 14040969
Permit Number 14040969
Review Stop B
Sequence Number 1
Notes
Date Text
2014-04-29 17:55:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. EGRESS IS SHOWN AS A SCREEN INSTALLED OVER AN
 OUTSWING DOOR. PROVIDE A DETAIL TO SHOW HOW THE DOOR
 WILL OPERATE WITH THE SHUTTER INSTALLED. INSTALLATION
 SCHEDULE INDICATES THAT THE SHUTTER GLASS SEPARATION IS
 0. SEE FBC 2010 RESIDENTIAL 310.4.
  
 2. SPANS NOT CLEAR. FOR INSTANCE, SEE OPENING 1. A
 40X66 (WXH), VERTICAL INSTALLATION, 4" EDGE DISTANCE,
 SHOULD HAVE A SPAN BETWEEN 66" AND 74", DEPENDING ON
 INSTALLATION METHOD, BUT SPAN IS 40" ON THE
 INSTALLATION SCHEDULE. SHUTTER MOUNTING CONNECTION TYPE
 IS NOTED AS "TYPICAL", BUT "TYPICAL" IN THE PRODUCT
 APPROVAL INCLUDES MANY DIFFERENT OPTIONS. REVISE SPANS
 AND PROVIDE MORE SPECIFIC INFORMATION IF NECESSARY.
  
 3. FASTENER PROPOSED NOT CLEAR. SEE PAGE 2; FOUR
 DIFFERENT TYPES OF LAGS WITH DIFFERENT LIMITATIONS.
 REVISE FASTENER TO BE SPECIFIC AS TO WHICH OF THE FOUR
 LAGS IS PROPOSED.
  
 4. EDGE DISTANCE IS 4", FOR WOOD, NOT CLEAR IF THIS IS
 POSSIBLE. THIS WOULD REQUIRE 8" OF STRUCTURAL WOOD
 SUBSTRATE, TOP AND BOTTOM, BUT THIS IS NOT TYPICAL OF
 WOOD FRAME STRUCTURES. PLEASE CLARIFY OR REVISE.
  
  
  