2014-04-25 08:57:14 | HAVING NOT INDICATED THE LOCATION OF THE AIR HANDLING | | UNIT, I MADE MENTION OF THE FOLLOWING REQUIREMENTS: | | HVAC EQUIPMENT INSTALLED IN ATTICS ARE SUBJECT TO | | SPECIFIC NEC | | REQUIREMENTS: | | NEC 110.33(B) REQUIRES A PERMANENT LADDER TO THE ATTIC | | NEC 210.63 REQUIRES A SERVICE OUTLET INSIDE THE ATTIC | | NEC 210.70 REQUIRES THAT THERE BE A LIGHT INSIDE THE | | ATTIC & | | NEC 410.11 REQUIRES THAT THE LIGHT HAVE A GUARD AROUND | | THE LAMP | | |
|