2014-06-18 11:04:21 | BECAUSE THIS IS A MASTER PERMIT PROVISOS OR REDLINES |
| ARE NOT ACCEPTED. THIS IS A MODEL FOR THE ENTIRE |
| PROJECT THEREFORE ALL ITEMS SHALL BE AS PER CODE FOR |
| APPROVAL. |
| |
| MOST OF THE ITEMS INITIALLY MENTIONED HAVE BEEN |
| ADDRESSED WITH THE EXCEPTION OF THE OUTLET PLACEMENT |
| PER NEC 210.52(A)(1) & (A)(2). IN A NUTSHELL EVERY WALL |
| GREATER THAN 2' INCLUDING THE AREA AROUND A CORNER |
| SHALL HAVE AN OUTLET. THERE CAN'T BE A DISTANCE GREATER |
| THAN 6' MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF A |
| WALL WITHOUT AN OUTLET. |
| NEC 406.11 REQUIRES THAT THE RECEPTACLE BE RATED "TR" |
| TAMPER-RESISTANT. IN ADDITION TO THIS, CONFIRM THE |
| COMPLIANCE WITH THE ARC-FAULT REQUIREMENTS OF NEC |
| 210.12(B). |
| |
| IN ADDITION TO THE ABOVE; IN THE INTEREST OF ENERGY |
| CONSERVATION AND LIFE SAFETY AS WELL AS OCCUPANT |
| CONVENIENCE, I SUGGESTED THAT ADDITIONAL SWITCHING |
| CONTROLS BE ADDED. IT IS MY BELIEF THAT EVERY HABITABLE |
| ROOM WITH MULTIPLE ENTRY/EXIT POINTS SHOULD HAVE ROOM |
| TRAVERSE LIGHTING CONTROL AT EVERY ENTRY/EXIT POINT. |
| |
| IF YOU HAVE ANY QUESTION, THESE PLANS WERE REVIEWED BY |
| MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER |
| YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE |
| FOLLOWING LINK: |
| HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT |
| US.ASPX |
| ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS |
| EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, |
| AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB |
| ABOVE THE SECOND PERMIT INFORMATION). |
| AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR |
| COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER |
| PERMIT CONDITIONS. |
| FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. |
| I CAN BE REACHED AT 561-805-6718 OR |
| [email protected] |