Plan Review Notes For Permit 14040895
Permit Number 14040895
Review Stop B
Sequence Number 2
Notes
Date Text
2014-06-27 10:26:322010 FBC
 REVIEWED UNDER 2010 FBC RESIDENTIAL FOR FEE SIMPLE
 TOWNHOUSES.
 TYPE VB CONSTRUCTION
 2 STORY, UNSPRINKLERED
 NO ELEVATORS
 OCCUPANCY TYPE IS R-3
  
 "MASTER PERMIT" FOR THE 8 UNIT TOWNHOUSE BUILDING AT
 CHARLESTON COMMONS
  
 DENIED BY BUILDING
  
 1) THE SUB-SURFACE SOIL REPORTS FOR THE PROJECT
 SPECIFIES THAT THE PREPARED SOIL WILL HAVE A BEARING
 CAPACITY OF 2000 PSF AND THE PLAN COVER SHEET STATES
 THAT THE DESIGN SOIL BEARING CAPACITY IS 2500 PSF. FBC
 R401.4
  
 2) SPECIFY THE CONNECTORS THAT WILL BE USED TO ANCHOR
 THE TRUSSES TO THE LEDGER ON THE INTERIOR WALL AT THE
 END UNITS A AND F. FBC R107.2.1.3
  
 3) SUBMIT TWO SETS OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. FBC R301.2.1.2 SPECIFY
 THE MOUNT TYPE, CONNECTION TYPE, SHUTTER SPAN,
 SEPARATION DISTANCE, ANCHOR TYPE, ANCHOR SPACING, ETC.
 AN INSTALLATION SCHEDULE FORM IS AVAILABLE ON THE
 CONSTRUCTION SERVICES HOME PAGE.
 WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP THE
 INSTALLATION SCHEDULES THAT WERE SUBMITTED ARE NOT
 CORRECT. PLEASE CORRECT.
  
 4) THE DESIGN PRESSURES IN THE PRODUCT APPROVAL, NOA
 NO. 12-0127.04 FOR THE LAWSON SLIDING GLASS DOOR ARE
 NOT ADEQUATE FOR THE 8' X 8' SGD. THE REQUIRED NEGATIVE
 OPENING PRESSURE IS - 47.1 PSF AND THE DESIGN PRESSURE
 FROM THE NOA IS - 43.0 PSF. I DID NOT FIND NEW PRODUCT
 APPROVALS IN THE RESUBMITTAL DOCUMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
2014-06-18 11:03:17 
  