Plan Review Notes For Permit 14040895 |
Permit Number |
14040895 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-05-30 19:01:58 | 2010 FBC | | | | PLUMBING DENIED | | | | 1) ALL OF THE UNITS THAT ARE SHOWN ON SHEET P1.0, HAVE | | IMPROPERLY VENTED BATHROOM GROUPS. SEE FBCR P3108.2.1 | | HORIZONTAL WET VENT. NOT MORE THAN ONE WET-VENTED | | FIXTURE DRAIN SHALL DISCHARGE UP-STREAM OF THE | | DRY-VENTED FIXTURE DRAIN CONNECTION. | | | | 2) ON THE MODEL F RISER DIAGRAM THE TUB IS NOT SHOWN AT | | THE END OF THE 2" HORIZONTAL DRAIN IN BATH #2. CITY | | AMENDMENTS 107.2.1 | | | | 3) ON THE MODEL A RISER DIAGRAM THE MASTER BATH SHOWER | | IS LABELED AS A TUB. CITY AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|