Plan Review Notes For Permit 14040895
Permit Number 14040895
Review Stop M
Sequence Number 1
Notes
Date Text
2014-06-02 08:19:552010 FBC
  
 DENIED BY MECHANICAL
  
 1) MODELS "A" AND "D" HAVE A 10" SUPPLY TO THE MASTER
 BEDROOM SUITE AND A 12" TRANSFER DUCT FOR THE RETURN,
 WHICH IS TOO SMALL. FBCR M1602.4 REQUIRES THE TRANSFER
 DUCT TO BE 1.5 TIMES THE CROSS SECTIONAL AREA OF THE
 SUPPLY DUCT SERVING THE MASTER SUITE AND THE DOOR
 HAVING A ONE INCH UNDERCUT.
  