Plan Review Notes For Permit 14040895 |
Permit Number |
14040895 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-06-02 14:36:08 | 2010 FBC | | REVIEWED UNDER 2010 FBC RESIDENTIAL FOR FEE SIMPLE | | TOWNHOUSES. | | TYPE VB CONSTRUCTION | | 2 STORY, UNSPRINKLERED | | NO ELEVATORS | | OCCUPANCY TYPE IS R-3 | | | | "MASTER PERMIT" FOR THE 8 UNIT TOWNHOUSE BUILDING AT | | CHARLESTON COMMONS | | | | DENIED BY BUILDING | | | | 1) SUBMIT TWO SETS OF A SITE PLAN FOR THE PROJECT THAT | | SHOWS THE LOCATIONS OF ALL OF THE PROPOSED | | IMPROVEMENTS. CITY AMENDMENTS 107.2.1 | | | | 2) SUBMIT TWO SETS OF SIGNED AND SEALED SUB-SURFACE | | SOIL REPORTS FOR THE PROJECT. FBC R401.4 | | | | 3) SUBMIT TWO SETS OF SIGNED AND SEALED TRUSS DRAWINGS | | FOR THE 8 UNIT BUILDING. REQUIRED FOR MASTERED PLANS. | | FBC R107.2.1.3 | | | | 4) SUBMIT TWO SETS OF A KEY PLAN AND INSTALLATION | | SCHEDULE FOR THE STORM PANELS. FBC R301.2.1.2 SPECIFY | | THE MOUNT TYPE, CONNECTION TYPE, SHUTTER SPAN, | | SEPARATION DISTANCE, ANCHOR TYPE, ANCHOR SPACING, ETC. | | AN INSTALLATION SCHEDULE FORM IS AVAILABLE ON THE | | CONSTRUCTION SERVICES HOME PAGE. | | WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | 5) THE DESIGN PRESSURES IN THE PRODUCT APPROVAL, NOA | | NO. 12-0127.04 FOR THE LAWSON SLIDING GLASS DOOR ARE | | NOT ADEQUATE FOR THE 8' X 8' SGD. THE REQUIRED NEGATIVE | | OPENING PRESSURE IS - 47.1 PSF AND THE DESIGN PRESSURE | | FROM THE NOA IS - 43.0 PSF. | | | | 6) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE SIMPSON | | CONNECTORS AND STRAPS AS REQUIRED BY DCA RULE 9N-3. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|