Plan Review Notes For Permit 14040889 |
Permit Number |
14040889 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-04-30 13:29:54 | AS NOTED BELOW, THIS HAD INITIALLY FAILED BUT AFTER | | SPEAKING W/MIKE OF CONTRACTORS ALARMS HE EXPLAINED THE | | METHODOLOGY OF HIS BATTERY CALCS TO A POINT THAT WAS | | UNDERSTOOD AND SUBSEQUENTLY APPROVED. | 2014-04-30 10:32:38 | THE FOLLOWING ITEMS NEED CORRECTION FOR APPROVAL: | | 1. THE SUBMITTED BATTERY CALCULATIONS ARE NOT CORRECT | | AND DO NOT MATCH THE JOB OR RISER DIAGRAM. CORRECT | | ACCORDINGLY | | 2. AS PER NFPA 72 SECTION 5.13.6, MANUAL FIRE ALARM | | PULL BOXES SHALL BE LOCATED WITHIN 5 FT. OF THE EXIT. | | THERE IS A PULL STATION TOWARDS THE REAR OF THE | | PREMISES THAT DOES NOT APPEAR TO BE WITHIN THE 5 FT | | REQUIREMENTS. RELOCATE ACCORDINGLY. | | I SPOKE W/ADRIANNE OF CONTRACTOR'S ALARM TO ADVISE OF | | STATUS. | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | CONTACT: | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | PH: (561) 805-6718, EMAIL: [email protected] | | |
|