Plan Review Notes
Plan Review Notes For Permit 14040889
Permit Number 14040889
Review Stop E
Sequence Number 1
Notes
Date Text
2014-04-30 13:29:54AS NOTED BELOW, THIS HAD INITIALLY FAILED BUT AFTER
 SPEAKING W/MIKE OF CONTRACTORS ALARMS HE EXPLAINED THE
 METHODOLOGY OF HIS BATTERY CALCS TO A POINT THAT WAS
 UNDERSTOOD AND SUBSEQUENTLY APPROVED.
2014-04-30 10:32:38THE FOLLOWING ITEMS NEED CORRECTION FOR APPROVAL:
 1. THE SUBMITTED BATTERY CALCULATIONS ARE NOT CORRECT
 AND DO NOT MATCH THE JOB OR RISER DIAGRAM. CORRECT
 ACCORDINGLY
 2. AS PER NFPA 72 SECTION 5.13.6, MANUAL FIRE ALARM
 PULL BOXES SHALL BE LOCATED WITHIN 5 FT. OF THE EXIT.
 THERE IS A PULL STATION TOWARDS THE REAR OF THE
 PREMISES THAT DOES NOT APPEAR TO BE WITHIN THE 5 FT
 REQUIREMENTS. RELOCATE ACCORDINGLY.
 I SPOKE W/ADRIANNE OF CONTRACTOR'S ALARM TO ADVISE OF
 STATUS.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  