2014-05-21 12:03:49PLUMBING PLAN REVIEW
 REVISION: 14040884
 PERMIT: 13120972
 ADD: 5802 S DIXIE HWY.
 CONT: MIKE MOORE
 TEL: (561)301-9468
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WEDNESDAY MAY 21/2014
 ACTION: PROVISO
  
 1) THIS IS A EXPANSION OF A INTERIOR- DEMO PERMIT TO
 INCLUDE THE REBUILDING OF A RESTROOM, THIS TENANT SPACE
 IS TO BE CONSIDERED A SHELL OR VANILLA BOX .PLEASE NOTE
 THE REQUIREMENTS FOR THE FOLLOWING OCCUPANCIES FOR A
 FUTURE TENANT BUILD OUT:
 . NOTE TENANT SPACE IS APPROXIMATELY 1386 SQ FT.
 BUSINESS 1386 SQ FT/ 100= 14 OCCUPANT LOAD 2010 FBC-P
 403.2 EXC 3 ALLOWS FOR A SINGLE UNISEX
  
 MERCANTILE 1386 SQ FT / 30 = 47 OCCUPANT LOAD 2010
 FBC-P 403.2 EXC 3 ALLOWS FOR A SINGLE UNISEX & HI-LOW
 DRINKING FOUNTAIN.
  
 MERCANTILE (RESTUARANT , 50 OCC) 1386 SQ FT / 30 = 47
 OCCUPANT LOAD 2010 FBC-P 403.2 EXC 3 ALLOWS FOR A
 SINGLE UNISEX, SERVICE SINK & GREASE INTERCEPTOR SIZED
 FOR FLOW RATE
  
 RESTAURANT 1386 SQ FT/ 15= 93 OCCUPANT LOAD REQUIRING 2
 RESTROOMS, SERVICE SINK & GREASE INTERCEPTORSIZED FOR
 FLOW RATE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  