Plan Review Notes For Permit 14040884 |
Permit Number |
14040884 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-04-29 16:13:16 | THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL, | | WITH THE FOLLOWING COMMENT. | | | | THE WALLS OF THE SPACE INDICATED AS "FUTURE A/C" SHALL | | HAVE A 1 HOUR RATING AND INDICATED AS SUCH ON THE PLAN. | | | | PER SECTION 8.7, ANY AREA HAVING A DEGREE OF HAZARD | | GREATER THAN NORMAL TO THE GENERAL OCCUPANCY OF THE | | BUILDING, SHALL BE PROVIDED WITH A 1-HOUR FIRE-RATED | | BARRIER OR BE PROTECTED WITH AN AUTOMATIC SPRINKLER | | SYSTEM. | | | | DENIED |
|