Plan Review Notes For Permit 14040828 |
Permit Number |
14040828 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-04-24 11:18:41 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS | | OR TEST REPORTS THAT CERTIFY THE PROFLEX 90 FLOOR TILE | | UNDERLAYMENT COMPLIES WITH FBC 1207.2 FOR AIR-BOURNE | | SOUND TRANSMISSION AND FBC 1207.3 FOR STRUCTURE BOURNE | | SOUND. | | | | 2) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS | | OR TEST REPORTS THAT CERTIFY THE PROFLEX 90 FLOOR TILE | | UNDERLAYMENT COMPLIES WITH FBC 603.1 (2) FOR | | COMBUSTIBLES IN TYPE I AND TYPE II CONSTRUCTION. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|