Plan Review Notes
Plan Review Notes For Permit 14040756
Permit Number 14040756
Review Stop B
Sequence Number 2
Notes
Date Text
2014-05-19 13:08:37RE-ROOF SECOND BUILDING REVIEW CHECKLIST.
 CODE; 2010 FBC.
  
 ***INFORMATION SUBMITTED TODAY IS THE SAME INFORMATION
 THAT WAS DENIED THE FIRST TIME. NEED TO ADDRESS THE
 COMMENTS FROM THE FIRST CHECKLIST.
  
  
 FLAT ROOF:
  
 1- SELECTED ASSEMBLY ON PAGE 27 OF NOA 13-0204.03
 SUBMITTED CAN'T BE USED. THIS ASSEMBLY IS LIMITED BY
 GENERAL LIMITATION #9. THIS LIMITATION DOESN'T ALLOW
 FOR NAIL ENHANCING TO COMPLY WITH THE DESIGN PRESSURES
 OF SEC. 1609 FBC. NEED TO SELECT ANOTHER APPROVED
 ASSEMBLY.
  
 2- ARCHITECT TO REVISE THE RAS 117 CALCULATIONS
 SUBMITTED. IF THE SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES CALCULATED FOR THE ROOF ZONE #1, THEN
 THE SELECTED ASSEMBLY CAN'T BE USED. SELECTED ASSEMBLY
 IS FOR -45PSF. THE CALCULATED DESIGN PRESSURES FOR ZONE
 1 ARE 52.5PSF. REVISE AS REQUIRED. SEE SECTION 8.1 OF
 RAS 117 OF 2010 FBC-TEST PROTOCOLS HVHZ.
  
 3- ARCHITECT TO COORDINATE BASE SHEET FASTENING SPECS
 FOR ROOF ZONE #1 WITH THE FASTENING SPECS SHOWN ON THE
 SELECTED ASSEMBLY. IF THE BASE SHEET FASTENING SPECS
 DON'T MATCH THE FASTENING SPECS SHOWN ON THE PRODUCT
 APPROVAL SUBMITTED, THEN THE RAS 117 CALCULATIONS WON'T
 BE CORRECT. REVISE AS REQUIRED AND COORDINATE WITH ITEM
 # 2 ABOVE. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712