Plan Review Notes For Permit 14040756 |
Permit Number |
14040756 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-04-23 16:07:37 | RE-ROOF BUILDING REVIEW COMMENTS. | | CODE; 2010 FBC. | | | | | | FLAT ROOF: | | | | 1- SELECTED ASSEMBLY ON PAGE 27 OF NOA 13-0204.03 | | SUBMITTED CAN'T BE USED. THIS ASSEMBLY IS LIMITED BY | | GENERAL LIMITATION #9. THIS LIMITATION DOESN'T ALLOW | | FOR NAIL ENHANCING TO COMPLY WITH THE DESIGN PRESSURES | | OF SEC. 1609 FBC. NEED TO SELECT ANOTHER APPROVED | | ASSEMBLY. | | | | 2- ARCHITECT TO REVISE THE RAS 117 CALCULATIONS | | SUBMITTED. IF THE SELECTED ASSEMBLY DOESN'T MEET THE | | DESIGN PRESSURES CALCULATED FOR THE ROOF ZONE #1, THEN | | THE SELECTED ASSEMBLY CAN'T BE USED. SELECTED ASSEMBLY | | IS FOR -45PSF. THE CALCULATED DESIGN PRESSURES FOR ZONE | | 1 ARE 52.5PSF. REVISE AS REQUIRED. SEE SECTION 8.1 OF | | RAS 117 OF 2010 FBC-TEST PROTOCOLS HVHZ. | | | | 3- ARCHITECT TO COORDINATE BASE SHEET FASTENING SPECS | | FOR ROOF ZONE #1 WITH THE FASTENING SPECS SHOWN ON THE | | SELECTED ASSEMBLY. IF THE BASE SHEET FASTENING SPECS | | DON'T MATCH THE FASTENING SPECS SHOWN ON THE PRODUCT | | APPROVAL SUBMITTED, THEN THE RAS 117 CALCULATIONS WON'T | | BE CORRECT. REVISE AS REQUIRED AND COORDINATE WITH ITEM | | # 2 ABOVE. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|