2014-05-12 16:30:50 | ELECTRICAL PROVISO: | | | | 1) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY | | AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS | | THAT SERVING THE NORMAL LIGHTING IN THE AREA AND | | CONNECTED AHEAD OF ANY LOCAL SWITCHES. 2008 EDITION OF | | THE NEC ARTICLE 701.11(G) | | | | 2) OCCUPANCY SENSORS REQUIRED IN ACCORDANCE WITH | | FBC-ENERGY CODE SECTION 505.2.2 PROVIDE AUTOMATIC | | LIGHTING SHUTOFF. | | |
|