Plan Review Notes
Plan Review Notes For Permit 14040710
Permit Number 14040710
Review Stop E
Sequence Number 1
Notes
Date Text
2014-05-12 15:26:29ELECTRICAL PROVISO.
  
 1) DRINKING FOUNTAIN REQUIRED BY FL ACCESSABILITY CODE.
 SEE BUILDING AND PLUMBING COMMENTS.
  
 2) RECEPTACLES FOR WATER COOLERS SHALL BE GFI
 PROTECTED. SEE ARTICLE 422.52 OF THE 2008 EDITION OF
 THE NEC.
  
 3) OCCUPANCY SENSORS REQUIRED IN ACCORDANCE WITH FBC-EC
 505.2.2 PROVIDE AUTOMATIC LIGHTING SHUTOFF.
  
 DAVID A. HAYES, ELECTRICAL PLANS EXAMINER.
 [email protected] 561-508-6717
  