Plan Review Notes For Permit 14040710 |
Permit Number |
14040710 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-05-12 15:26:29 | ELECTRICAL PROVISO. | | | | 1) DRINKING FOUNTAIN REQUIRED BY FL ACCESSABILITY CODE. | | SEE BUILDING AND PLUMBING COMMENTS. | | | | 2) RECEPTACLES FOR WATER COOLERS SHALL BE GFI | | PROTECTED. SEE ARTICLE 422.52 OF THE 2008 EDITION OF | | THE NEC. | | | | 3) OCCUPANCY SENSORS REQUIRED IN ACCORDANCE WITH FBC-EC | | 505.2.2 PROVIDE AUTOMATIC LIGHTING SHUTOFF. | | | | DAVID A. HAYES, ELECTRICAL PLANS EXAMINER. | | [email protected] 561-508-6717 | | |
|