2014-05-08 19:28:13FAILED FIRST ELECTRICAL REVIEW AS MENTIONED BELOW:
 AS PER THE 2008 EDITION OF THE NEC THE FOLLOWING
 CORRECTIONS SHALL BE MADE TO THE SUBMITTED PLANS FOR
 APPROVAL
 1. PER NEC 210.8 ALL OUTLETS IN THE KITCHEN AREA SHALL
 BE GFCI PROTECTED.
 2. PER NEC 210.12 ARC-FAULT PROTECTION IS REQUIRED IN
 THE KITCHEN AS WELL
 3. REMOVE FROM THE GENERAL ELECTRICAL NOTES ITEMS
 NUMBERED 6, 7, 16, 18, 19 WHICH DO NOT APPLY. YOU MAY
 WANT TO CORRECT THE TYPO ON #14 AS WELL.
 4. ALL NEW AND EXISTING OUTLETS IN THE WORK AREA SHALL
 BE MADE COMPLIANT WITH NEC 314.21. THEREFORE THE EC
 SHALL VERIFY WITH THE GC THE KIND OF BACK SPLASH AND/OR
 WALL COVERING FOR THE FINISHED WALL.
 5. IF BLDG. HAS DEDICATED LAUNDRY FACILITIES, SO
 INDICATED. OTHERWISE INCLUDE THE LAUNDRY LOAD AS PART
 OF THE LOAD CALCS.
 6. THE 10KW HEAT HAS A 10KW LOAD. REWORK YOUR LOAD
 CALCS ACCORDINGLY.
  