2014-04-29 08:22:44PLUMBING PROVISO;
 SHOWER LINER TEST REQUIRED.
 312.9 SHOWER LINER TEST.
 WHERE SHOWER FLOORS AND RECEPTORS ARE MADE WATER-TIGHT
 BY THE APPLICATION OF MATERIALS REQUIRED BY SECTION
 417.5.2, THE COMPLETED LINER INSTALLATION SHALL BE
 TESTED. THE PIPE FROM THE SHOWER DRAIN SHALL BE PLUGGED
 WATER TIGHT FOR THE TEST. THE FLOOR AND RECEPTOR AREA
 SHALL BE FILLED WITH POTABLE WATER TO A DEPTH OF NOT
 LESS THAN 2 INCHES (51 MM) MEASURED AT THE THRESHOLD.
 WHERE A THRESHOLD OF AT LEAST 2 INCHES (51 MM) HIGH
 DOES NOT EXIST, A TEMPORARY THRESHOLD SHALL BE
 CONSTRUCTED TO RETAIN THE TEST WATER IN THE LINED FLOOR
 OR RECEPTOR AREA TO A LEVEL NOT LESS THAN 2 INCHES (51
 MM) DEEP MEASURED AT THE THRESHOLD. THE WATER SHALL BE
 RETAINED FOR A TEST PERIOD OF NOT LESS THAN 15 MINUTES,
 AND THERE SHALL NOT BE EVIDENCE OF LEAKAGE.