Plan Review Notes For Permit 14040680 |
Permit Number |
14040680 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-04-29 08:22:44 | PLUMBING PROVISO; | | SHOWER LINER TEST REQUIRED. | | 312.9 SHOWER LINER TEST. | | WHERE SHOWER FLOORS AND RECEPTORS ARE MADE WATER-TIGHT | | BY THE APPLICATION OF MATERIALS REQUIRED BY SECTION | | 417.5.2, THE COMPLETED LINER INSTALLATION SHALL BE | | TESTED. THE PIPE FROM THE SHOWER DRAIN SHALL BE PLUGGED | | WATER TIGHT FOR THE TEST. THE FLOOR AND RECEPTOR AREA | | SHALL BE FILLED WITH POTABLE WATER TO A DEPTH OF NOT | | LESS THAN 2 INCHES (51 MM) MEASURED AT THE THRESHOLD. | | WHERE A THRESHOLD OF AT LEAST 2 INCHES (51 MM) HIGH | | DOES NOT EXIST, A TEMPORARY THRESHOLD SHALL BE | | CONSTRUCTED TO RETAIN THE TEST WATER IN THE LINED FLOOR | | OR RECEPTOR AREA TO A LEVEL NOT LESS THAN 2 INCHES (51 | | MM) DEEP MEASURED AT THE THRESHOLD. THE WATER SHALL BE | | RETAINED FOR A TEST PERIOD OF NOT LESS THAN 15 MINUTES, | | AND THERE SHALL NOT BE EVIDENCE OF LEAKAGE. |
|