2014-04-22 13:46:49NEC
  
 310.15(B)(6)
 CONDUCTOR MATERIAL, SIZE AND INSULLATION TYPE SHALL BE
 ADAQUATE FOR THE LOAD TO BE SERVED.
  
 230.90(A)
 THE OCPD CAN NOT EXCEED THE CAPACITY OF THE SERVICE
 CONDUCTOR
  
 FBC 107.2.1
 CONSTRUCTION DOCUMENTS SHOULD BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF WORK
 PROPOSED. PLEASE PROVIDE A PANEL SCHEDULE FOR NEW MAIN
 BREAKER PANEL INDICATING SIZE AND RATING OF ALL OCP
 DEVICES AND WHAT THEY SERVE.
  