Plan Review Notes
Plan Review Notes For Permit 14040657
Permit Number 14040657
Review Stop E
Sequence Number 3
Notes
Date Text
2014-06-04 14:44:22PROJECT: 5335 N. MILITARY TR. #40 AND 65
 PERMIT# 14040657
 3RD ELECTRICAL REVIEW
 ACTION: PROVISIONAL APPROVAL
 CODE: 2008 NEC AND 2010 FBC
  
 CORRECTIONS REQUIRED ON REVISION:
  
 1) A BUILDING OR OTHER STRUCTURE SERVED SHALL BE
 SUPPLIED BY ONE SERVICE UNLESS PERMITTED IN 230.2(A)
 THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2
 ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND
 LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED
 TOGETHER AT THEIR SUPLY END BUT NOT CONNECTED TOGETHER
 AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING
 ONE SERVICE. NEC 230.2 (NUMBER OF SERVICES)
 THE RISER AND FLOOR PLAN AS CURRENTLY SHOWN ON SHEET
 E-1 INDICATES THIS EXACT CONDITION PROHIBITED BY THE
 CODE NOTED ABOVE. PLEASE MAKE CORRECTION TO THIS
 CONDITION AND RE-SUBMIT.
  
 1) RECEPTACLES FOR WATER COOLERS SHALL BE GFI
 PROTECTED. SEE ARTICLE 422.52 OF THE 2008 EDITION OF
 THE NEC.
  
 2) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY
 AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES. SEE ARTICLE
 701.11(G) OF THE 2008 EDITION OF THE NEC.
  
 3) CHILD CARE FACILITIES SHALL COMPLY WITH THE 2010
 EDITION OF THE FBC SECTION 436 SEE SECTION BELOW:
 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM SHALL BE
 BY MANUAL MEANS AND BY OPERATION OF ANY REQUIRED SMOKE
 DETECTORS AND REQUIRED SPRINKLER SYSTEMS. FBC 436.7.1
  
 4) OCCUPANT NOTIFICATION SIGNALS SHALL BE AUDIBLE AND
 VISUAL SIGNALS IN ACCORDANCE WITH NFPA 72 AND THE
 FBC-ACCESSIBILITY. THE GENERAL EVACUATION ALARM SIGNAL
 SHALL OPERATE THROUGHOUT THE ENTIRE BUILDING. FBC
 436.7.1.1
  
 5) A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN
 EACH STORY IN FRONT OF DOORS TO STAIRS AND IN THE
 CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAYCARE
 OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN
 LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY
 CARE OCCUPANCY. 436.7.2
  
 6) SEPARATE ELECTRICAL PERMITS ARE REQUIRED FOR LOW
 VOLTAGE SCOPE INCLUDING SECURITY ALARM, CCTV, FIRE
 ALARM, DATA/COM, AND ACCESS CONTROL,
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]